Installation manual

39
Operation and Installation Manual for SOLIVIA 2.0/2.5/3.0/3.3/3.6/5.0 EU G4 TR
8. Commissioning
EN
-------------------
continue
PDD: Standard
-------------------
PDD settings
9. Press the buttons to select continue and then
press the
button.
If the PDD setting is User, an extended PDD Set-
tings menu will be displayed. Continue with Step 10.
If the PDD setting is Standard or Off, the Locked
Power Limit menu will be displayed. Continue with
Step 12.
continue
Umax: 253V
-------------------
PDD settings
10. To change the value, press the button and then set
the value using the
buttons. Press the button to
apply the value.
NOTE: Steps 10 and 11 are only
necessary when the mode User was
set in Step 9.
Available Umax settings:
253 - 264 V (corresponds to 110 -
115% of 230 V), default is 253 V.
-------------------
continue
Umax: 253V
-------------------
PDD settings
11. Press the buttons to select more and then press
the
button.
The Locked Power Limit menu is displayed.
Smax: _._kVA
Pmax: _._kW
-------------------
Locked power limit
12. To change the value, press the button and then set
the value using the
buttons. Press the button to
apply the value.
NOTE: If you change one of the val-
ues, you must ll out the provided
label after commissioning and place it
next to the type plate
NOTE: The congured values can
only be changed with a PIN after com-
missioning.
NOTE: The congured values are
displayed after commissioning in the
131 View Grid Setup menu.
continue
Smax: _._kVA
Pmax: _._kW
-------------------
-------------------
Locked power limit
13. Press the buttons to select more and then press
the
button.
The Power Balancing menu is displayed.
continue
Balancing: Off
-------------------
Power balancing
14. To change the settings, press the button and then
select the option using the
buttons. Press the
button to apply the setting.
NOTE: The grid load can only be
balanced with a SOLIVIA Gateway M1
G2. If no gateway is connected, the
Balance option will always be set to
Off. Otherwise the solar inverter will
not feed into the grid.
-------------------
continue
Balancing: Off
-------------------
Power balancing
15. Press the buttons to select continue and then
press the
button.
The Format menu is displayed.
Time: 24h
Date: DD.MM.YYYY
-------------------
Format
16. To change the value, press the button and then set
the value using the
buttons. Press the button to
apply the value.
Available date formats:
DD.MM.YYYY | DD/MM/YYYY
DD-MM-YYYY | MM.DD.YYYY
MM/DD/YYYY | MM-DD-YYYY
YYYY.MM.DD | YYYY/MM/DD
YYYY-MM-DD
Available time formats:
12h | 24h
continue
Time:
24h
Date: 25.05.2012
-------------------
-------------------
Format
17. Press the buttons to select continue and then
press the
button.
The Date and Time menu is displayed.