Operation and Installation Manual for SOLIVIA 2.0/2.5/3.0/3.3/3.6/5.0 EU G4 TR
7. Installation
EN
recommend using a 20 A residual current device. However, be
sure to always adhere to the specic regulations applicable in your
country.
The typical leakage current is less than 3.5 mA.
NOTE
The rated value of the secondary short-circuit
current at the grid connection point to the public
power grid increases due to the rated current of
the connected solar inverter.
To protect the user and the system, install the required safety and
protection devices (e.g., automatic circuit breaker and/or overvolt-
age protection devices).
A special kit for France is available from Delta. This kit contains all
components required to meet the requirements specied in UTE
C15-712-1 (“16.1 Order numbers”, p. 82).
7.3.2 Required Tools and Accessories
Included in delivery:
Round AC plug
Wieland RST25i3S
Not included in delivery:
Flexible triple-core cable (L, N, PE) with a conductor cross-
section from 2.5 mm
2
to 4 mm
2
Cable end sleeves suitable for the conductor cross-section.
Cable strain-relief.
Locking washer for connecting the ground wire to the solar
inverter (see Fig. 7.4, p. 27, item C).
7.3.3 Establishing Connection
1. Remove the cable sheath as shown and remove 10 mm of
insulation from each wire end.
NOTE
Observe the correct polarity of the round
plug. An incorrect conguration can destroy
the solar inverter.
10 mm
52,5 mm (PE: 57,5 mm)
2. Place the end sleeves on the exposed wire ends and crimp
them on.
3. Connect the AC cable to the AC plug as described below.
Unscrew the nut
from the cable housing and then remove
the cable housing from the socket insert .
1.
2.
Slide the nut and cable housing onto the AC cable.