Installation manual
90
Technicaldata
15EUG4TL 20EUG4TL
Max. Operating Altitude 2000 m
MECHANICALDESIGN
Size (L x W x D) 952 x 625 x 275 mm
Weight 67.2 kg 67.2 kg
Enclosure Powder coated aluminum
Cooling Fan
AC connector Amphenol C16-3
DC connector pairs 4 Multicontact MC4
Communication interfaces 2 RJ45 / RS485
DC disconnector Integrated
Display Black / white graphical LCD
STANDARDS/DIRECTIVES
Protection degree
3)
IP55 lower section / IP65 upper section (see gure 4-1 for
further detail)
Safety class 1
Congurable trip parameters Yes
Insulation monitoring Yes
Overload behavior Current limitation, power limitation
Safety IEC62109-1 / -2, AS/NZS 3100
Grid Interface VDE-AR-N 4105, BDEW, VDE 0126-1-1; G59/2; EN 50438;
UTE C15-712-1, Synergrid C10/C11 (fullls C10/C11 transi-
tional rule from June 2012), RD661, RD1699, CEI 0-21,
TERNA A70, AS 4777
EMC EN61000-6-2; EN61000-6-3; EN61000-3-11; EN61000-3-12,
C-Tick
1)
The maximum AC apparent power indicates the power an inverter is able to deliver. This maximum apparent power may not
necessarily be reached.
2)
AC voltage and frequency range will be programmed according to the individual country requirements.
3)
IP55 for cooling section / IP65 for electronics
11.2 CableRecommendations
Powerwiring
Current rating Cross-section Recommended max. cable
loss calculation
AC 30 A Calculated based on needed
length, used material, cable
losses and etc.
<1 %
DC 30 A 6 mm
2
<1 %
Communicationcable
RS485 modular communication cable / cross wired 8 poles