Installation manual

69
ENGLISH
OperatingthePVinverter
Parameter Adjustablevalues CurveA CurveB
Lock-in Voltage* 230-253 V 241.5 V is default value and is 1.05Vn (Vn =
230V)
Lock-out Voltage* 207-230 V 230 V is default value (adjustable at 0.98 Vn
to Vn; Vn=230V). When the grid voltage ≤ the
Lock-out voltage
Mode ON I OFF This switches the feature on and off. Default
mode is OFF.
*These values are only adjustable if Country setting is Italy CEI-021 or Italy A70. This means the
inverter will feed in reactive power depending on the active power once the grid voltage is higher
than Lock-in Voltage. When grid voltage is lower than Lock-out voltage then inverter would go
back to pure active power control.
For countries other than Italy, cos φ(P) control would not be effected by the grid voltage.
6.3.6.4.5ConstantReactivePower
This feature is available for Italy CEI 0-21 and Italy A70.
This feature allows a constant cos reactive power to be set.
Figure 6.33.: Constant Reactive Power settings page
Adjustableparameters
Parameter Adjustablevalues Description
Reactive power Q/Sn -60 ... +60% Reactive power ratio in relation to apparent
power. Enter the value requested by the grid
operator
inductive | capacitive
Mode ON I OFF This switches the feature on and off
6.3.6.4.6Q(V)
This feature is available for Italy CEI 0-21 and Italy A70.