Installation manual
65
ENGLISH
OperatingthePVinverter
Note: For explanation of Actual vs Rated
Power please see gure 6.18.
Figure 6.28.: Power Limit settings page
Adjustableparameters
Parameter AdjustableValues Description
Set point 0 ... 100% Sets the power reduction to the adjusted value.
The value is multiplied with the value of the
Locked power limitation.
Actual/Rated Actual | Rated Select Actual or Rated Power
Mode ON | OFF Switches the feature on and off.
6.3.6.4.2Powervs.Frequency
This function is available for CEI 0-21 and A70. The gure below explain the behavior of this func-
tion. Note that the Italy CEI 0-21 and A70 curves are different than the Germany LVD and MVD
curves.
This feature allows the user to set a power reduction in a percent of the maximum power.