Installation manual
64
OperatingthePVinverter
Note: User can activate both the Power
Limit and the Power vs. Frequency at the
same time.
For the reactive power control features:
cosφ(P), Constant Reactive Power, and
Q(V) only one of these items can be activa-only one of these items can be activa-
ted at a time.
p indicates a function is executing
* This feature is disabled for CEI 0-21 and
A70 although it will appear in the menu
Figure 6.27.: Active/Reactive Power settings page
Note: Before adjusting the Active/Reactive Power settings, a Warning window will be displayed,
that you should read and make a selection to continue or to quit. Please see caution messages
related to adjusting the settings.
CAUTION
Machineandequipmentdamagemayoccur.
► Please only adjust active and reactive power settings if you are a quali-
ed electrical technician with the knowledge to do so
► Adjustments may affect energy production
► Some values entered in the Active/Reactive Power settings must come
from the local grid operator. Please check with them before making any
adjustments
6.3.6.4.1PowerLimit
User can select set percentage of actual or rated power to limit inverter’s output power. Inverter
will start the action once the user sets the Mode to “ON”. This feature is available for Italy CEI
0-21 and Italy A70.