Installation manual
61
ENGLISH
OperatingthePVinverter
Figure 6.25.: Q(V) settings page
Adjustableparameters
Parameter MenuName Adjustablevalues Description
Lower Q/Sn Qi Limit 0 ... 60% Must be within the range Ind 60%
... Cap 60%
inductive | capacitive
Upper Q/Sn Qs Limit 0 ... 60% Must be within the range Ind 60%
... Cap 60%
inductive | capacitive
Lower capaci-
tive point
V2i 184 ... 264 V
Upper capaci-
tive point
V1i 184 ... 264 V For DE MVD the default V1i =
V1s = 230 V
Lower inductive
point
V1s 184 ... 264 V
Upper inductive
point
V2s 184 ... 264 V
Delay time 0 ... 10 s
Lock-in Power not applicable Not used for DE MVD
Lock-out Power not applicable Not used for DE MVD
Mode ON I OFF This switches the feature on and
off
6.3.6.3.7FaultRideThrough(FRT)
This feature is available for MVD grids only.
This feature allows the Fault Ride Through features to be set.