Installation manual
59
ENGLISH
OperatingthePVinverter
Figure 6.23.: cos φ(P) settings page
Adjustableparameters
Parameter Adjustablevalues Description
Upper limit - cos φ Ind 0.80 ... Cap 0.80 The upper limit cos φ must be greater than the
lower limit cos φ
Lower Power 0 ... 100 %
Lower limit - cos φ Ind 0.80 ... Cap 0.80
Upper Power 0 ... 100 % The upper power must be greater than the lower
power
Lock-in Voltage Not used for DE LVD/MVD
Lock-out Voltage Not used for DE LVD/MVD
Mode ON I OFF This switches the feature on and off
6.3.6.3.5ConstantReactivePower
This feature is available for MVD grids only.
This feature allows a constant cos reactive power to be set.