Installation manual

58
OperatingthePVinverter
6.3.6.3.3Constantcosφ
This feature is available for LVD and MVD grids. This feature allows the user to set up a constant
cos φ.
Figure 6.22.: Constant cos φ settings page
Adjustableparameters
Parameter Adjustablevalues Description
cos φ inductive | capacitive Sets the cos φ to the adjusted value.
Ind 0.8 ... Ind 0.99, 1,
Cap 0.8 ... Cap. 0.99
Mode ON | OFF Switches the feature on and off
6.3.6.3.4
cosφ(P)
This feature is available for LVD and MVD grids.
With this feature a cos φ can be assigned to a power ratio P/Pn.
The following curve is an example how the values could be set: