Installation manual
53
ENGLISH
OperatingthePVinverter
Password is 5555.
Figure 6.14.: Install Settings Page - Installer Mode
● InverterID:This setting is used to set unique ID‘s for installations with more than one
inverter. In a multi-inverter installation where the inverters will be in a network, each inverter
must have a unique ID.
● Insulation: ON means enable the measurement of impedance between Array and PE, will
not connect to Grid if failure. Depending on DC wiring conditions, user can set 6 kind of
insulation detecting method - ON, Positive Ground, Negative Ground, DC1 only, DC2 Only, or
Disable. Installer can select different resistance criteria according the actual conditions.
● Country: This is the Country selected during startup (nonadjustable).
Figure 6.15.: Insulation Settings - Installer Mode
6.3.6.3
Active/Reactive Power control for DE LVD and DE MVD
Below is an overview of the features that are adjustable to control the production of active and
reactive power for Germany LVD and MVD
Feature Availablefor Description
LVD MVD
Active power control