Installation manual
41
ENGLISH
WiringtheInverter
Figure 5.12.: Terminal Resistor Switch for Multi-inverter Connection
To engage the internal Terminal Resistor, place switch number 2 on the communication module in
the on position.
Baud Rate Programmable, 2400/4800/9600/19200/38400, default = 19200
Data Bit 8
Stop Bit 1
Parity N/A
Table 5.3.: RS485 Data Format
5.5.2 EPO(EmergencyPowerOff)Connections
The SOLIVIA 15 TL and 20 TL provides emergency power off functions by using an RJ45 connec-
tor. When the outer external switch is shorted, the inverter will shut down immediately. Please see
Table 5.4 for the pin de nition.
PIN Denition
1 EPO1
2 EPO1
3 N/A
4 EPO2
5 EPO2
6 N/A
7 N/A
8 N/A
Table 5.4.: EPO pin assignment