Installation manual
36
WiringtheInverter
NOTE
The fans shown are without the required protective screen for illustrative
purposes
CAUTION
Machineandequipmentdamagemayoccur.
► The connection number of PV ARRAY, open circuit voltage and power
of String_1 and String _2 must be coherent.
► The connection number of PV ARRAY, open circuit voltage and power
of String _3 and String _4 must be coherent.
► The maximum power connected to the 15 TL may not exceed 10 kWp
per input or 19 kWp in total.
► The maximum power connected to the 20 TL may not exceed 13 kWp
per input or 25 kWp in total.
► The maximum open circuit voltage of PV Array must not exceed 1000 V.
► The range of V
mpp
of Input DC1 and Input DC2 shall be 350~800 V
DC
.
► The device installed between PV array and inverter must meet the rat-
ing of voltage <1000 V
DC
and < short current.
Cablesize:
Currentrating Wiresize
DC 30 A 6 mm
2
/ 10 AWG
DC wiring polarity is divided into positive and negative, which is shown in gure 5-6. The connec-
tion should be consistent with the indicated polarity marked on the inverter.
Figure 5.7.: DC Wiring Illustration