Installation manual
34
WiringtheInverter
Figure 5.5.: AC plug illustration
CAUTION
Machineandequipmentdamagemayoccur.
► Observe the pin assignment of the AC bayonet connector. An incorrect
assignment can result in the unit being destroyed. The Figure 5.5 pin
out diagram shows the connections inside the AC connector.
NOTE
Make sure the line is provided with a strain relief device. When using cables
with a diameter of less than 13 mm (11mm...13mm diameter cable
require strain relief), the cable must be relieved just behind the connector.
The connection to the Amphenol AC connector for both models can be made with a exible or
rigid cable with a copper conductor that has a cross section greater than 4.0 mm
2
and which has
an installation condition that gives a correction factor equal to one. The AC cable should be pro-
tected by a minimum type B 40 Amp breaker.
This connector is developed for connection to copper wires (for other applications please contact
Amphenol). The cross section of the cable should be calculated by considering the material used,
thermal conditions, length of the cable, the type of installation, and AC voltage drop.
Please note the cable length and the cable cross-section, due to the risk of undesirable tempera-
ture rise and power losses. In some countries (e.g. France, Germany) system installation require-
ments have to be followed (UTE 15712-1, VDE 0100 712). This recommendation will dene mini-
mum cable sections and protections against overheating due to high currents. Please make sure
that you follow specic requirements in your country.
For the security of your installation and for the safety of the user, please install required safety and
protection devices that are applicable for your installation environment (example: automatic circuit
breaker and/or overcurrent protection equipment).
WARNING
Deathandseriousinjurymayoccur
In the case of damage or bodily harm resulting from the use of this device
in a way contrary to it’s intended purpose or as a result of unauthorized
modications made to the parameters of the inverter, Delta will not be held
liable in these situations..
The solar inverter must be grounded via the AC connector’s PE conductor. To do this, connect the
PE conductor to the designated terminal.
The AC connector is protected from unintentional disconnection by a clip mechanism which can
be released with a screwdriver.