Installation manual
31
ENGLISH
WiringtheInverter
CurrentRating Wiresize Torque
≤ 30 A 6mm
2
/ 10 AWG ≥ 0.9 Nm (10 kg)
AC wiring can be separated into 3-phase (L1, L2, L3), N, and PE. The following earthing congu-
rations are allowed. IT is not allowed. Please see the appendix for further explanation of these
earthing systems.
TN-S TN-C TN-C-S TT IT
Yes Yes Yes Yes No
Table 5.1.: Permitted earthing systems
NOTE
TT ist not recommended. Have to besure the voltage of N is very close to
PE (< 20 V
rms
)
In Figure 5.5, the Amphenol C16-3 AC connector shown can be mated with the inverter‘s AC plug.
After disassembly of the connector, please adhere to the correct polarity for proper AC wiring (this
product allows either positive or negative phase sequence). That means the sequence of L1-L3
can be adjusted and the N and PE must be connected.
5.2.1 ACbayonetconnector
The AC bayonet connector is approved for cable sheath diameters between 11 mm and 20 mm.
To install an AC cable, rst strip the voltage free line and cable ends as shown below and then
follow the sequence in Figure 5.5 to assemble the cable and bayonnet connector.
52.5mm(PE57.5mm)
10mm
Figure 5.3.: AC cable stripping requirements
NOTE
For lines with a cable sheath diameter from 16 mm to 20 mm, the cable
gland must be adapted accordingly. To do this, cut out the inner section of
the blue sealing ring.