Mode Tiger Dimmable Power Unit MODE LIGHTING (UK) LIMITED The Maltings, 63 High Street, Ware, Hertfordshire, SG12 9AD, England. Tel: +44 (0) 1920 462121 e-mail: sales@modelighting.
TIGER INSTALLATION MANUAL TP-10-06 and TP-06-09 Page 1. Contents 2. Introduction 3. Installation procedure 4. Mechanical fixing 5. Identification of terminals TP-10-06 (6 channel) 6. Identification of terminals TP-06-09 (9 channel) 7. Mains supply wiring 8. Output wiring TP-10-06 (6 channel) 9. Output wiring TP-06-09 (9 channel) 10. Control wiring - low voltage 11. Control module settings 12. Power module functions 13. Indicator identification 14.
INTRODUCTION "Reliability from Mode" MODE POLICY: To create superior products and to provide our customers with long term reliability, serviceability and value for money. The Company does not make economies which are of short term benefit only. FOUNDATION: Mode was established in 1970 as an Original Equipment Manufacturer in Hertfordshire, England. Mode designs and manufacturers in the U.K.
INSTALLATION PROCEDURE 1. Remove all packaging. 2. Read instructions and retain for future reference. 3. Fit unit to wall and observe spacing instructions. 4. Remove front plate and store in a safe place. 5. Fit trunking (4" minimum) to desired option. 6. Install all input supply wiring to National Wiring Regulations and other applicable Regulations. 7. Install all output load wiring to National Wiring Regulations and other applicable Regulations. 8. Install all low voltage control wiring.
MECHANICAL FIXING Mark positions, drill holes and fit screws to wall, see diagram below. Dimensions in millimetres. Hang unit on screws and tighten. 322 302 534 452 Use screws with minimum size No.8 x 1 1/2" NOTE : When positioning holes, take into account that the unit will drop 10mm lower due to the keyhole fixing slots WARNING: Allow 300mm top and at least 40mm side clearance between the side flanges and any other object. This unit must be mounted vertically.
IDENTIFICATION OF TERMINALS TP-10-06 (6 CHANNEL) PHASE INPUT NEONS DMX / SCENARIO INPUT TERMINALS ANALOGUE INPUT / OUTPUT TERMINALS EMERGENCY TERMINALS AND MCBÌS START ADDRESS AND FUNCTION SWITCHES CHANNEL OUTPUT TERMINALS MAINS INPUT TERMINALS 5
IDENTIFICATION OF TERMINALS TP-06-09 (9 CHANNEL) PHASE INPUT NEONS DMX / SCENARIO INPUT TERMINALS ANALOGUE INPUT / OUTPUT TERMINALS EMERGENCY TERMINALS AND MCBÌS START ADDRESS AND FUNCTION SWITCHES CHANNEL OUTPUT TERMINALS MAINS INPUT TERMINALS 6
MAINS SUPPLY WIRING This unit is to be wired by a suitably qualified electrician in accordance with National Wiring Regulations and other applicable Regulations. TERMINALS Three Live phase input terminals (20 amp max.). One Neutral input terminal (60 amp max.). One Earth input terminal (60 amp max.). TERMINAL SPECIFICATIONS Terminal Wire sizes mm2 Stranded Solid Strip length mm Tightening torque Nm lb/in Phase 1 Phase 2 Phase 3 4 - 16 4 - 16 4 - 16 4 - 25 4 - 25 4 - 25 14 14 14 1.2 - 1.4 1.2 - 1.
OUTPUT WIRING TP-10-06 (6 CHANNEL) This unit is to be wired by a suitably qualified electrician in accordance with National Wiring Regulations and other applicable Regulations. CHANNEL OUTPUT TERMINALS 6 Live output terminals (10 amp max.). 6 Neutral output terminals (10 amp max.). One 15 way Earth common bars (10 amp max.). CONNECTION Connect loads using wire of between the values stated below and in accordance with the calculated loadings.
OUTPUT WIRING TP-06-09 (9 CHANNEL) This unit is to be wired by a suitably qualified electrician in accordance with National Wiring Regulations and other applicable Regulations. CHANNEL OUTPUT TERMINALS 9 Live output terminals (6.6 amp max.). 9 Neutral output terminals (6.6 amp max.). One 15 way Earth common bars (6.6 amp max.). CONNECTION Connect loads using wire of between the values stated below and in accordance with the calculated loadings.
CONTROL WIRING (LOW VOLTAGE) EXTERNAL CONNECTORS (top plate) RS-232 9 way D connector - for future use. 5 Pin XLR chassis socket for DMX connection. Connections:- DMX+ = pin 3, DMX - = pin 2, Screen = pin 1. 5 Pin XLR chassis plug for DMX connection. + - Connections:- DMX = pin 3, DMX = pin 2, Screen = pin 1. 25mm conduit entry for hard wired control cables.
CONTROL MODULE SETTINGS Display showing start address. Scenario data indicator. Data error indicator. DMX data received indicator. Push button increment 100's for start address. Push button increment 10's for start address. Push button increment 1's for start address. For future use. DIP switches - RIGHT=ON. 1 - 6 / 9 channels (6 = off ). 2 - Digital / Analogue ( Analogue = off ). 3 - 6V / 10V Operation ( 6V = off ). 4 - DMX / RS232 ( DMX = off ). 5 - Set DMX terminator, not used in Scenario systems.
POWER MODULE FUNCTIONS TWIN MODULE used in 6 channel model TP-10-06 Heatsink and mounting bracket RFI noise suppression chokes Channel mains feed indicators 2 (green) User replaceable triac Channel control signal indicators 2 (red) Output pre heat adjustment control Set switch point for switching channels Set alarm enable for selected channel Set a channel to switch or dim Module full on test switch TRIPLE MODULE used in 9 channel model TP-06-09 Heatsink and mounting bracket RFI noise suppression chokes Ch
INDICATOR IDENTIFICATION The three neons shown indicate when the phase input is live. Phase 1 Phase 2 Phase 3 TP-10-06 (6 channel) The two green neons shown indicate when the channel input is live i.e. when the MCB is on. The two red LED's indicate a control signal is present. These still operate if the mains to the module is not switched on. TP-06-09 (9 channel) The three green neons shown indicate when the channel input is live i.e. when the MCB is on.
TECHNICAL SPECIFICATION TP-10-06 (6 CHANNEL) POWER SUPPLY Voltage 230V AC nominal. (207V - 253V), 50Hz. (110V 60Hz AC nominal available to order) Single phase neutral and earth - three 20 amp live feeds. Three phase neutral and earth Star configuration - 20 amp/phase. (Three phase Delta configuration available to order) Connection - hard wired to din rail mounting screw terminals. TOTAL CURRENT 60 AMP. DIMMING OUTPUTS Hard fired leading edge triac triggering.
TECHNICAL SPECIFICATION TP-06-09 (9 CHANNEL) POWER SUPPLY Voltage 230V AC nominal. (207V - 253V), 50Hz. (110V 60Hz AC nominal available to order) Single phase neutral and earth - three 20 amp live feeds. Three phase neutral and earth Star configuration - 20 amp/phase. (Three phase Delta configuration available to order) Connection - hard wired to din rail mounting screw terminals. TOTAL CURRENT 60 AMP. DIMMING OUTPUTS Hard fired leading edge triac triggering. Maximum load 6.
MAINTENANCE Periodically inspect the wiring for damage. Ensure the ventilation holes have not become covered or blocked with dust. Check overall condition of unit.
Mode Lighting (UK) Limited was established in 1970 as a manufacturer of electronic componets for the lighting industry. Mode has an enviable reputation for quality, reliability and customer service. The Mode Group employs more than 140 people in over 10,000m2 of well equipped factories, offices and warehouses. Products include:Electronic Transformers for Low Voltage. Electronic Cold Cathode Convertors. Architectural Dimming Systems. Electronic Ballasts. LED Systems.