User manual

Chapter 1 TPEdit Operation
1-41
Step 7. Check “Call” and press to choose to call which reference device. And
select “after writing” or “before writing” to Set or Reset. For example, if the
reference device is Y3 and check “after writing” to “set”. It will inform Y3 to
set after pressing the button.
Step 8. Font is used to set the text on the button. Its size is usually set to 8X12. You
could also select figure to put on button. You could select no frame, single
frame, double frame, circle frame and hidden for the button. If you select
hidden, the button won’t have any frame on the TP page but it still has the
same function when executing.
Step 9. If you press BMP read, you will get the open dialog box. You could set the
corresponding bitmap for the current state.
Step 10. After setting and press OK, the button will be used according to the setting
unction.
Multi-state: press this button and TP will send the signal to the PLC corresponding
contact or register. The signal could be cycle through S0 S1 S2
S0 or S0 S2 S1 S0. The max. state
could be 256 (VALUE), 16 (LSB) and 2 (BIT).
Value: Press this button and TP will display built-in value on screen. You could use
function key or common key to enter value. When pressing Enter, TP will send
value to PLC corresponding register.