Latched button: the contact will be ON when you press and hold on. Once
you release the button, the contact is OFF.
Step 1. Choose Object (O
) > Button and move the mouse to the editing area. At the
moment, the mouse pointer will be cross pointer. You could press the mouse
and hold on to drag, once you release the button the component
will be displayed.
Step 2. Double-click left button and you will get the following dialog box.
Step 3. Pressing button at the right side of “Button Type” to select Interactive.
Step 4. Pressing
button at the right side of “Write” to select the reference device to
write. And pressing
button at the right side of “Read” to select the
reference device to read.
Step 5. Check Fun. Key and press
to select one of F0~F9. Please notice that
function keys F5~F9 should be used with Shift key. You should set it by
yourself, if you don’t set it and you can’t control the button component.
Step 6. Password setting is used to protect this button. If you set password for the
button, you should enter correct password before executing the button
function.
Step 7. Check “Call” and press
to choose to call which reference device. And
select “after writing” or “before writing” to Set or Reset. For example, if the
reference device is Y3 and check “after writing” to “set”. It will inform Y3 to set