Table of Contents Chapter 1 Overview and Installation ............................................................... 1-1 1-1 Hardware Features ............................................................................. 1-1 1-1-1 TP04G Components...................................................................................... 1-1 1-1-2 TP04G Keys .................................................................................................. 1-2 1-2 Mounting .......................................
Content 2-3-6 Language Settings ........................................................................................ 2-8 2-3-7 Password Settings......................................................................................... 2-8 2-3-8 Start-up Display............................................................................................. 2-9 Chapter 3 TPEdit Operation............................................................................ 3-1 3-1 Hardware ............................
Preface Preface The TP series is a small HMI (human machine interface) with big features. It allows users to monitor and control PLCs, Variable Frequency Drives, and other controllers. The TP series may also be purchased with graphic capabilities (TP--G models). The TP series products are programmed using the TPEdit software. Getting Started Users should read the entire manual before using the TPEdit software or TP series hardware.
Chapter 1 Overview and Installation Chapter 1 Overview and Installation Features of TP04G: ! ! ! ! ! ! ! Monitoring programming and controlling PLCs, AC drives or other controllers. There are three built in languages to choose from (Traditional Chinese, Simplified Chinese and English, the factory setting is English). Built-in RS232 and RS485 communication ports. Built-in RTC with perpetual calendar function. Display has auto power off energy saving function.
Chapter 1 Overview and Installation Chart 1-1 Explanation of TP04G components Back Panel Front Panel Components Explanation Display area of A 128*64 resolution of yellow-green back-light LCD (Liquid Text and graphics Crystal Display). LED Standard LED functions: power on indication, communication indication, and a user-defined indication. Status 1: When power is on, LED will start blinking slowly. Status 2: When it is abnormal, LED will light every second along with the audible alarm.
Chapter 1 Overview and Installation Command key Button Explanation ENTER Used to enter new data or confirm a message ESC Used to change the mode between user program mode and system menu mode. Also to escape an incorrect entry. UP ARROW Up key may be used to increase a value or to move to the upper page. DOWN ARROW Down key may be used to decrease a value or to move to the lower page. LEFT ARROW Left key is used to choose the decimal place of a number.
Chapter 1 Overview and Installation 1-2-2 Mounting Mounting TP04G into the opening is done by carefully fitting the unit into the opening and pressing firmly on all four corners. Thickness:1.0〜4.0mm 1-3 Connection The TP04G may connect to a Delta DVP-PLC via a DVPACAB215 cable (Note 1). It may also connect to other PLCs or AC drives using a user supplied cable. The TP series may connect to more than one device using the 2-wire RS485 connection.
Chapter 1 Overview and Installation 1-3-3 Programming Connection The TP04G may use the RS232 or RS485 to connect to a PC. recommended connection is using the RS232 port and a DVPACAB215 cable. The 1-4 Power connection TP04G requires a 24VDC at 150mA power source for operation. Proper grounding is required to filter any electrical noise and make sure the hardware components work normally. 1-5 Cleaning When cleaning the TP04G, please use soft cotton cloth and water.
Chapter 2 TP04G Operation and Settings Chapter 2 TP04G Operation and Settings This chapter will introduce the two working modes of the TP04G: ! System main menu mode: users can change the settings of the HMI using five main menus. This chapter will discuss the content and function of each menu, and teach you how to use the TP04G. ! Display monitor mode: this will display on screen status of devices connected to the TP04G (ex: PLC, AC drives or other hardware devices).
Chapter 2 TP04G Operation and Settings Waiting for Communicating... Time Out Esc : Escape Enter : Retry ! The following display is shown when the communication is complete. Communication is Completed. Esc : Escape 2-2-2 Upload TP04G -->PC Allows the user to send a program from the TP04G to the PC for reviewing or updating. After choosing option 2, the TP04G will wait for the PC (TPEdit software) to send a ready message and then the TP04G will display the data receive status bar during communication.
Chapter 2 TP04G Operation and Settings 2-2-3 Copy TP04G <-->TP04G ! The Copy function allows the user to move a program from on TP04G to another TP04G via communication. Connection must be done, using twisted pair wire connected between two TP04G RS485 communication ports. ! Below is a pictorial description of the process. 1. Download TP04G <-- PC 2. Upload TP04G --> PC 3 . Copy TP04G <--> PC 4. TP04G Settings 5. Execute ENTER 1. Transmit Program 2.
Chapter 2 TP04G Operation and Settings 2-2-4 TP04G Settings ! When choosing option 4 “TP04G Settings”, there will be two displays (8 total options) to choose for set up. 1. Download TP04G <-- PC 2. Upload TP04G --> PC 3. Copy TP04G <--> PC 4 . TP04G Settings 5. Execute 1. Communication Protocol 2. Contrast 3. Back-lighted 4. Date and Time ENTER 5. Buzzer 6. Language Settings 7. Password Settings 8. Start-up Display ! Please refer to section 3 for details of the TP04G set-up menu.
Chapter 2 TP04G Operation and Settings Communication Protocol 1. TP04G Settings 2. RS232 3. RS485 TP04G Settings ENTER 1. Communication address 001 2. PLC Control Port RS232 ! Communication Address: Users may use the left, right, F0-F4 and Shift F0-F4 keys to change the value of communication address. The left and right keys are used to choose the integer location, and the F0-F4 keys are used to select a value of the integer.
Chapter 2 TP04G Operation and Settings RS232 1. Transmission Rate 2 . Data Length 3. Parity Check 4. Stop Bit 9600 7-bit Even 1-bit ENTER < RS232 1. Transmission Rate 2. Data Length 3. Parity Check 4. Stop Bit ! Parity Check: The Left or Right arrow will scroll from Even to None, Odd. complete press the Enter key. RS232 1. Transmission Rate 2. Data Length 3 . Parity Check 4. Stop Bit 9600 7-bit Even 1-bit ENTER < RS232 1. Transmission Rate 2. Data Length 3. Parity Check 4.
Chapter 2 TP04G Operation and Settings 1. Communication Protocol 2. Contrast 3 . Back-lighted 4. Date and Time ENTER Back-lighted Auto Close 05 minutes ! The factory setting is 01 minute. The available range is 00~99 minutes. A setting of 00 will cause the Back Light to never turn off. 2-3-4 Date and Time 1. Communication Protocol 2. Contrast 3. Back-lighted 4 . Date and Time ENTER Date and Time 1. Date 2003/01/10 2. Day FRI 3.
Chapter 2 TP04G Operation and Settings 5. Buzzer 6. Language Settings 7. Password Settings 8. Start-up Display Buzzer ENTER 1. Normal 2. Mute ! Use the Up or Down arrow to choose Normal or Mute. the Enter key. 2-3-6 When complete press Language Settings 5. Buzzer 6 . Language Settings 7. Password Settings 8. Start-up Display Language Settings ENTER 1. English 2. Traditional Chinese 3. Simplified Chinese 4. User-defined ! You can select a language by using the UP or Down keys.
Chapter 2 TP04G Operation and Settings 2-3-8 Start-up Display 5. Buzzer 6. Language Settings 7. Password Settings 8 . Start-up Display Start-up Display ENTER 1. TP04G Settings 2. User-defined ! TP04G settings are the factory default display. ! The User defined settings are based on the display created in the TPEdit software. 2-9 DELTA ELECTRONICS, INC.
Chapter 3 TPEdit Software Operation Chapter 3 TPEdit Software Operation 3-1 Hardware requirement Operation system requirement for installing TPEdit should be: Items Operation system CPU Memory Hard disk capacity Display resolution Mouse Printer RS-232 System requirement Windows 95/98/2000/NT/XP Pentium 90 or above 16MB or above (32MB and above is recommended) 20MB or above 640x480, 16 colors and above Compatible with Windows Compatible with Windows At least one Com Port to connect to TP04G 3-2 Installati
Chapter 3 TPEdit Software Operation ! Press Next> for following steps to go to next step ! Enter user name and company name. User name Company name DELTA ELECTRONICS, INC.
Chapter 3 TPEdit Software Operation Press Next> to go to the following window for installing. 3-3 DELTA ELECTRONICS, INC.
Chapter 3 TPEdit Software Operation After finishing installing, user can execute TPEdit from windows> start. 3-3 Basic Introduction TPEdit is the program editor for DELTA PLC series use in WINDOWS. You can see the design result on the screen immediately by concept of “What You See is What You Get” that TPEdit adopts. What you see on the screen is what display on HMI. TPEdit uses object-oriented method to reach drag edition.
Chapter 3 TPEdit Software Operation Mouse Pointer Name Arrow pointer !、" Resize pointer ! I Cross pointer I pointer Functions The position where the mouse is. It will display on the border of windows or object when adjusting size. It will display when opening object or drawing. It will display when editing text.
Chapter 3 TPEdit Software Operation The start-up display of TPEdit will be shown as follows. There are four functions in menu bar for you to select. After opening file, you should set machine setting, including PLC or Inverter type, TP type and file name. At the moment, you can select other functions in menu bar. We will introduce them later. 3-5-2 Menu Bar Overview File (F) DELTA ELECTRONICS, INC.
Chapter 3 TPEdit Software Operation ! Create a new project ! Open an old project ! User Menu Set: users can set the languages or menu depends on requirement. ! Save: save the file into disk. ! Save as: save the present file to other file name. ! Print: print present file and set printer settings. ! Close Project: close present project. ! Exit: exit TPEdit. Edit(E) ! Add new page ! Jump page: input the jump page condition. If the condition is held, it will jump to the designated page.
Chapter 3 TPEdit Software Operation ! Undo: back to the previous condition. ! Redo: do the condition before redo. (this item is for future edition) ! Delete: delete the component in editing page. ! Cut: delete and cut the component in editing page. ! Copy: copy the component in editing page. ! Paste: paste the component to editing page. ! Select all: select all components in editing page.
Chapter 3 TPEdit Software Operation ! Static Text: edit text to shown on TP04G screen. ! Value Show: HMI reads PLC corresponding value of register to show on HMI screen. ! Bit Light: HMI reads the corresponding contacts (ON or OFF) or register data to show the corresponding figures on HMI screen. ! Figure: it is used to edit static figure to be the background.
Chapter 3 TPEdit Software Operation ! Tpe Page Manager: manage the edited page. ! Tpe Page: display edited HMI page and switch between HMI page and start-up display. ! Starting Figure: edit start-up display and switch between HMI page and start-up display. Transfer ! Tp data read out: Read application program from TP04G to TPEdit. ! Tp data write in: Write application program from TPEdit to TP04G. ! Starting figure write in: input start-up display that edited by TPEdit into TP04G.
Chapter 3 TPEdit Software Operation conditions of each page, the conditions of each page has high priority.) ! System Funkey set: it is used to define the button type and functions of function keys F0~F9. It doesn’t need to set in each page. Once the function keys F0~F9 are used, they will be executed according to the definition of button type and functions. (if the function settings of system conflicts with the function settings of each page, the function setting of each page has high priority.
Chapter 3 TPEdit Software Operation Windows: ! Tile Vert.: display edit page in vertical. ! Tile Horz.: display edit page in horizontal. ! Cascade: display edit page in overlay. Help: ! Version: display software version of TPEdit and relative information. ! Tpe Help: provide electronic file of TPEdit user manual. Above is the basic introduction of TPEdit. We will explain the functions that used frequently for detail in the following.
Chapter 3 TPEdit Software Operation Step 2. Enter machine type setting. Step 3. User can set PLC or Inverter Type, TP type and File Name in this dialog box. Step 4. You can use file name to record the function of program. For example, you can name ”MonitorProductionLine” for the program that monitors the production line. Step 5. TPEdit document usually have extension .tpe. TPEdit will name your new project to be Tpe0. (the default name will be Tpe0. tpe, Tpe1. tpe……in order.
Chapter 3 TPEdit Software Operation Method 1: Step 1. choose File (F) > Open an old project. Step 2. Open an old project dialog box. File name # key in or select the file name that you want to open. It will show all the file type that selected in “file type” in this dialog box. File type # select the file type you want to open: Tpe File (i.e. *.tpe) Search # select the disk or file that you want open. Method 2: Click the button to open the existed file. Method 3: Pressing〔Ctrl〕+〔O〕.
Chapter 3 TPEdit Software Operation Step 2. You can set the language you need here. But you can’t modify the function definition and button size. Step 3. You just need to double-click the item you want to modify and it will show the dialog box for you to edit. 3-15 DELTA ELECTRONICS, INC.
Chapter 3 TPEdit Software Operation PC in TP04G hardware main Step 4. After editing, press 1. download TP04G menu. The words “Waiting for communicating…” will be shown on HMI screen. Step 5. Choose Transfer(T) > Input User-defined Menu. This function just can be used under the mode of setting user menu. It is used to download the menu to TP04. Step 6. To set language you should select 6. language setting in TP04G main menu and then press Enter to set. Language Settings 5. Buzzer 6 . Language Settings 7.
Chapter 3 TPEdit Software Operation Method 3: Press〔Ctrl〕+〔S〕. ! Save as Save the present file in another name into disk. TPEdit will save new project to be the default name, if you want to save it to another name, please choose “Save as”. Step 1. Choose File (F) > Save as. Step 2. input file name and then save. 3-17 DELTA ELECTRONICS, INC.
Chapter 3 TPEdit Software Operation ! Print Step 1. Choose File (F) >Print. Step 2. You can check the print attribute you need in the following dialog box. DELTA ELECTRONICS, INC.
Chapter 3 TPEdit Software Operation ! Close Project Choose File (F) > Close Project to close the present project. ! Exit Choose File (F) > Exit or click not before exit TPEdit. 3-6-2 at the right upper-corner. Please confirm to save or Edit (E) In addition to undo, cute and paste functions of TPEdit, there are four functions (including add new page, jump page, alarm setting, alarm LED setting) you can use. We will explain these four functions in the following.
Chapter 3 TPEdit Software Operation Step 3. Click reference device to input device name, device number and communication address. The devices’ name that you can set in this window are X, Y, M, S, D, C and T and the equipment no. are 0~F. Select the reference device (In the “Jump Page Set” dialog box, it is different to set Bit or Value in condition Set. If you set to Bit, the device name you can select are X, Y, M, S, C and T. If you set to Value, the device name you can select are T, C and D.
Chapter 3 TPEdit Software Operation due to the default first page is number 0. You can set the value length and value type that you need in value setting. Value length could be 16-bit or 32-bit. Value type could be unsigned or signed decimal, hexadecimal or BCD. Condition could be =, <, >, >=, <= or !=. Step 5. After finishing input, press “Add in” to add. The condition will display in the message window.
Chapter 3 TPEdit Software Operation Step 6. After setting, press “Close” to return to editing page. ! Function Key Settings Step 1. Choose Edit (E) > Function Key Settings or click right button of mouse to get the pop-up menu to select function key settings. Step 2. And then you will get the following function key setting dialog box. ! Step 3. it is used to set button type of function key F0~F9. (you can refer to object setting.) Once you set a function key, you should press button “Set” to set.
Chapter 3 TPEdit Software Operation Step 3. The settings are the same as jump page settings. When the condition is held, buzzer will sound. ! Alarm LED Settings The settings of alarm LED are the same as alarm settings. Once the condition is held, the alarm LED will light. ! Save image of pages: Choose Edit (E) > Save image of pages to save the present image to clipboard or file. ! Undo, Redo: to back to the previous action or redo the action before execute “undo”.
Chapter 3 TPEdit Software Operation Choose Compile (C) > Compile or click the button to compile application program to transmit to TP04G. After compiling successfully, you will get the following dialog box. 3-6-4 Objects Function Explanation You could choose Object (O) or press ﹝ ALT ﹞ + ﹝ O ﹞ to set object. It is the management system for all objects. You need to open a page before using this function. DELTA ELECTRONICS, INC.
Chapter 3 TPEdit Software Operation ! Static Text Step 1. Choose Object (O) > Static Text or click the button . At the moment, the mouse pointer will be cross pointer. You can press the left button of mouse, drag to the position you need and then release to get the text square. Step 2. Move the mouse to static text square and then double-click left button of mouse to get the following window. 3-25 DELTA ELECTRONICS, INC.
Chapter 3 TPEdit Software Operation Step 3. You can input text and setting the font attributes (including frame setting, text direction, position and font type). Frame setting could be single frame, double frames, bold frames, dotted line frames or spotted line frames. Text direction could be from left towards to right, from right towards to left, from up towards to down and from down towards to up. Text position could be left side, right side or middle side.
Chapter 3 TPEdit Software Operation Step 2. Click reference device and you will get the following window. Step 3. In this dialog box, you could set device name to be T, C and D and device number to be 0~F. If your device name is AC driver, it doesn’t need to check device name. It will show symbol $ to mean AC driver absolute address. What you need is to input absolute address in device number. Step 4.
Chapter 3 TPEdit Software Operation Step 9. After setting, HMI will read PLC corresponding reference device to show the value on HMI screen. ! Bit Light There are two types for you to choose: State Show Setting: Choose Object (O) > Bit Light (16X16) > State Show or click the button to set. When HMI reads the PLC corresponding contacts (ON or OFF), it will show the corresponding figure. Range Light Setting: choose Object (O) > Bit Light (16X16) > Range Light or click the to set.
Chapter 3 TPEdit Software Operation ! Figure You could choose static figure or dynamic figure. Static Figure: choose Object (O) > Figure > Static figure or click the button . It will read the static figure to be the background of HMI. It just can read the file with extension .bmp now. Step 1. Choose Object (O) > Figure > Static figure and move the mouse to the editing area. At the moment, the mouse pointer will be cross pointer.
Chapter 3 TPEdit Software Operation TPEdit has built-in figures (including button type and arrows) for users to use. The built-in figures are saved in TPEdit\ BmpGroup. Dynamic Figure: Choose Object (O) > Figure > dynamic figure or click the button . HMI reads PLC corresponding reference register value will do comparison operation according to the corresponding base state. The setting figure will be displayed on the screen according to the operation result. (it you check bit, base state could be 0 or 1.
Chapter 3 TPEdit Software Operation Step 1. Choosing Object (O) > Figure > Dynamic figure and then move the mouse to the editing area. At the moment, the mouse pointer will be cross pointer and you could press left button and hold on to drag. Once you release the button, the action will be finished and the component will be displayed. Step 2. You could move the mouse to this component and double-click the left button to get the following dialog box. Step 3.
Chapter 3 TPEdit Software Operation Step 2. You could set scale position, progress direction, main scale, sub scale, Max. value, Min value, value length or font in the dialog box. Step 3. The graduation of scale could be face up, down, left or right. The progress direction could be Forward (increase from left to right or top to bottom), or reverse (increase from right to left or bottom to top). Step 4. Setting the precision of scale of main scale and sub scale. Step 5.
Chapter 3 TPEdit Software Operation and min value in the dialog box. Step 3. Progress set is used to set the direction for bar chart to increase and show on the HMI screen. Step 4. Max. value and min. value are the range for value to display. Only the value between max. and min. value will be shown on the bar chart. Step 5. After setting, HMI will read PLC corresponding register data and convert it to bar chart to show on HMI screen. ! Meter Step 1.
Chapter 3 TPEdit Software Operation ! Message Display Step 1. Choose Object (O) > Message Show or click the button following dialog box. to get the Step 2. HMI will read the PLC corresponding contacts (ON or OFF) or register data and display the corresponding status on HMI screen. The content of message could only be text and the text direction of LED message will be scrolls in a loop as follows: from right to left, from left to right, from top to bottom and from bottom to top. Step 3. The max.
Chapter 3 TPEdit Software Operation $ Latched button: the contact will be ON when you press and hold on. Once you release the button, the contact is OFF. Step 1. Choose Object (O) > Button and move the mouse to the editing area. At the moment, the mouse pointer will be cross pointer. You could press the mouse and hold on to drag, once you release the button the component will be displayed. Step 2. Double-click left button and you will get the following dialog box. Step 3.
Chapter 3 TPEdit Software Operation Step 8. Font is used to set the text on the button. Its size is usually set to 8X12. You could also select figure to put on button. You could select no frame, single frame, double frame, circle frame and hidden for the button. If you select hidden, the button won’t have any frame on the HMI page but it still has the same function when executing. Step 9. After setting and press OK, the button will be used according to the setting function.
Chapter 3 TPEdit Software Operation Increase/decrease button: pressing this button and HMI will read register data from PLC and add or submit according to the settings. It will write the result to PLC corresponding register. If you set 10 for inc/dec and 1000 for up/down bound, it means it will increase/decrease 10 for each time you press the button. And the maximum you can increase/decrease is 1000. Jump Page Set button: pressing this button and HMI will change to designate page.
Chapter 3 TPEdit Software Operation There are functions of password setting and inform command in the dialog box. You could use password setting to protect this button. And you could check “call” to set to call the reference device to reset to set before writing or after writing. ! Perpetual Calendar Choose Object (O) > Perpetual Calendar or click the button get the following dialog box. directly and you will You can set time relative, font, frame set and position set in the dialog box.
Chapter 3 TPEdit Software Operation ! Geometric Figure You could press the buttons directly and press the buttons the result that did with these tools. to use geometric to draw the line. The following page is ! Lamp Display Choose Object (O) > Lamp Display or click the button to get the following dialog box. The settings are the same as dynamic figure. The addition setting is text input. It is used to input text and edit text.
Chapter 3 TPEdit Software Operation You could set the measure type and measure unit you need. 3-6-5 View ! Page manager Choose View (V) > Page Manage and you will get the following dialog box. You could input page title to delete or add or insert that page or open all pages. ! HMI page Display HMI page and change the page between HMI page and start-up display. ! Start-up display It is used to edit start-up display and change the pages between start-up display and HMI display.
Chapter 3 TPEdit Software Operation ! User Menu Write in Choose Transfer (T) > User Menu Write in to edit user menu to input to TP04G. 3-6-7 Settings ! IDE Font Choose Setting (S) > IDE Font to get the following dialog box. User could set the font attributes. ! Communication Protocol Choose Setting (S) > Communication Protocol to get the following dialog box. You could set 0~255 to HMI communication address.
Chapter 3 TPEdit Software Operation ! Page Size Choose Setting (S) > Page Size to set page proportion. The setting could be 100%, 200% or 400%. ! Frame Setting Choose Setting (S) > Frame Setting to use grid as coordinate reference or not. ! System Page Jump Choose Setting (S) > System Page Jump to get the dialog box. You should notice that system page jump is the condition of change page of all pages but the condition of change page in Edit menu is only for the editing page.
Chapter 4 Communication Connection Mode Chapter 4 Communication Connection Mode Before any communication between the TP and TPEdit software is conducted, the user should complete the TP04G hardware settings and connect the correct wiring between the two components. There are three items in the communication protocol of TP series product that must be set for communication to work properly. ! The TP address and control port. ! The RS-232 settings. ! The RS-485 settings.
Chapter 4 Communication Connection Mode Communication methods: Step 1. After creating a display program, the program should be compiled before downloading to the TP04G. Select “Compile” in the menu bar to complete this task. Any errors in programming will be displayed after this process. Step 2. On the TP04G, select the “Download TP04G more information. PC.” Refer to Chapter 2 for Step 3.
Chapter 4 Communication Connection Mode It is receiving... 37% 4-3 DELTA ELECTRONICS, INC.
Chapter 4 Communication Connection Mode Step 4. Users may also read from the TP04G and display it on the TPEdit window. steps are similar to Downloading, except choose “TP data read out.” DELTA ELECTRONICS, INC.
Chapter 5 Examples Chapter 5 Examples Example 1. Edit start-up display Step 1. Open TPEdit to select File(F) to create new file. Then choose View(V)>start-up display and it will escape start-up display. Step 2. In edition display, you can choose static text or static graphics. If you choose static graphics, the mouse pointer will become to cross pointer in the working area. At this time, you can press the left button of mouse and hold on to drag.
Chapter 5 Examples Step 4. Click the button of “BMP Read” in above window and the following window will be shown. Please select the BMP file and click “Open (O)” button. Then click “Yes” button in the above window and the window of “Start-up Display” will be shown as following. Step 4. In TP04G, choosing 1. download program TP04G will show the words of “Waiting for communicating”. PC. On TP04G screen, it Step 5.
Chapter 5 Examples Example 2. To use TP04G to connect to two PLC and control their output contacts ON/OFF. Step 1. Choose File(F) to create a new file. Step 2. Model settings should be set as following: 1. PLC or Inverter model: You should choose “DELTA PLC-ES/EX/SS”, TP type: you should choose TP-04, File Name: you can name by yourself, here we name it “ Connection with two PLC” and then press “OK” to enter edit mode. 5-3 DELTA ELECTRONICS, INC.
Chapter 5 Examples Step 3. To choose ”Object(O)” and move mouse to working area. At this time, mouse pointer will be cross pointer. To press left button and hold on to drag and the component will show in window after you release the button. Step 4. Double-click the left button of the mouse and you can see the following window. Step 5. To click in the right side of button type and you can choose alternate type. Step 6.
Chapter 5 Examples clear to display. You can also put the figure on the button. Step 11. To press “OK” after finishing setting and this button will be used for the setting functions. Step 12. Choose “Compile” > “Compile” to compile the edition page. Step 13. In TP04G, choose “1. download program TP04G show “Waiting for communicating….“. PC” to download and it will Step 14. In TPEdit, to choose “Communicate” > “TP write in” and press “OK” to download program to TP04G. Step 15.
Chapter 5 Examples The first PLC Communication address=1 Slave Workstation TP04G Master Workstation The second PLC Communication address =2 Slave Workstation The N PLC Communication address =N Slave Workstation The max. PLC numbers that TP04G can connect is less than 255 PLCs. Master TP connects to slave PLC in series with RS485. In each PLC, you should give them a different communication address.
Chapter 5 Examples Step 3. To choose ”Object(O)” and move mouse to working area. At this time, mouse pointer will become to cross pointer. To press left button and hold on to drag and the component will show in window after you release the button. Step 4. Double-click the left button of the mouse and you can see the following window. Step 5. To click in the right side of button type and you can choose alternate type. Step 6.
Chapter 5 Examples Step 7. If you check the item of “Read” and press besides “Read”, it will also have the window of “Device reference”. The settings should be set as following window. Then press “OK” to escape this window. Step 8. The button setting is the same as example 2. The value length is set to 16 bits, the value type is hexadecimal, the function key can be F2 or others, button character is set to frequency input, integer number and decimal number are all set to 2. Max.
Chapter 5 Examples Step 9. If you want to read the information of frequency, you can check “Read” in above figure. The setting method is the same as “Write”. You can also set password for button function and press “OK” to return to edition page (as shown in the following figure). Step 10. Click “Compile” to compile the edition page. Step 11. Then select 1. Download TP04G <- PC on TP04G main menu. At this moment, TP04G will show “Wait for communicating….”. Step 12.
Chapter 5 Examples The 2nd PLC Communication address =2 Slave Workstation DELTA ELECTRONICS, INC.
Chapter 5 Examples The first PLC Communication address =1 Slave Workstation TP04G Master Workstation The 2nd AC drives Communication address =2 Slave Workstation The Nth PLC or AC drives Communication address =N Slave Workstation The max. PLC numbers that TP04G can connect is less than 255 PLCs. Master TP connects to slave PLC in series with RS485. In each PLC, you should give them a different communication address.
Chapter 6 Troubleshooting Chapter 6 Troubleshooting This chapter is used to solve the problems during operating TP04G. If the problem relates to PLC or AC drives, please refer to the PLC or AC drives relative manual. The following is the problem that may occur when using TP04G: 1. The message of communication time-out occurs when download or upload program. You should compiler program by choosing compiler > compiler in the TPEdit main menu or clicking after editing before download program to TP04G.
Chapter 6 Troubleshooting RS232 1. Transmission Rate 2. Data Length 3. Parity Check 4. Stop Bit 9600 7-bit Even 1-bit Please note that if you want to download or upload program, you should enter TP04G main menu to select 1. download program or 2. upload program and to get the following waiting display first. Then, you should select “Transfer”> “Tp data read out” or “Tp data write in” in TPEdit. Waiting for Communicating...
Chapter 6 Troubleshooting In the communication protocol setting, you should enter 1. TP04G communication setting and choose 2. PLC control port to set RS232 or RS 485 to connect to PLC. Then you can set the communication settings of RS232 or RS485. Please note that the settings should be the same as PLC communication protocol. RS 485 1. Transmission Rate 9600 1. TP04G Settings 2. Data Length 7-bit 2. RS232 3. Parity Check Even 3 . RS485 4.
Chapter 6 Troubleshooting Please note that the positive/negative electrode of RS485. If there is something wrong when communicating, please check if the positive/negative electrode of RS485 is correct. DELTA ELECTRONICS, INC.