Datasheet

TECHNICAL DATASHEET
CliQ DIN Rail
Power
Supply
24V 240W 1
Phase
/ DRP024V240W1AA
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (December 2012, Rev. 02)
4
Safety Standards / Directives
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety
SIQ to EN60950-1, UL/cUL recognized to UL60950-1,
CSA C22.2 No. 60950-1, CB scheme to IEC60950-1,
CSA to UL60950-1 and CSA C22.2 No. 60950-1
(File No. 181564)
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01,
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX
CSA to CSA C22.2 No. 213-M1987, ANSI / ISA
12.12.01:2007 (Class I, Division 2, Group A, B, C, D, T4)
EN60079-0:2009, EN60079-15:2010
( II 3G Ex nA IIc T4 Gc)
II 3G ATEX 94/9/EC;
IECEX Test Report
Certificate No. ESP 09 ATEX 1 215 X;
For IEC60079-0, IEC60079-15
CE
In conformance with EMC Directive 2004/108/EC and
Low Voltage Directive 2006/95/EC
Material and Parts
RoHS Directive 2011/65/EU Compliant
Galvanic Isolation
Input to Output
4.0KVac
Input to Ground
1.5KVac
Output to Ground
1.5KVac
EMC
EMC / Emissions
CISPR22, EN55022, EN55011, FCC Title 47: Class B
Immunity to
Electrostatic Discharge
EN61000-4-2
Level 4 Criteria A
1)
Air Discharge: 15kV
Contact Discharge: 8kV
Radiated Field
EN61000-4-3
Level 3 Criteria A
1)
80MHz1GHz, 10V/M with 1kHz tone / 80% modulation
Electrical Fast Transient / Burst
EN61000-4-4
Level 3 Criteria A
1)
2kV
Surge
IEC6100-4-5
Level 3 Criteria A
1)
Common Mode
2)
: 2kV
Differential Mode
3)
: 1kV
Conducted
EN61000-4-6
Level 3 Criteria A
1)
150kHz-80MHz, 10Vrms
Power Frequency Magnetic Fields
EN61000-4-8
Level 3 Criteria A
1)
10A/Meter
Voltage Dips
EN61000-4-11
Level 3 Criteria A
1)
100% dip; 1 cycle (20ms); Self Recoverable
Low Energy Pulse Test (Ring Wave)
IEC61000-4-12
Level 3 Criteria A
1)
Common Mode
2)
: 2kV
Differential Mode
3)
: 1kV
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)