The power behind competitiveness Delta UPS - Modulon Family NH Plus Series, Three Phase 20-120 kVA User Manual www.deltapowersolutions.
Save This Manual This manual contains important instructions and warnings that you should follow during the installation, operation, storage and maintenance of this product. Failure to heed these instructions and warnings will void the warranty. Copyright © 2012 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc. (“Delta”).
Contents Contents 0. Important Safety Instructions.......................................................................... 0-1 1. Introduction ...................................................................................................... 1-1 1-1 Advanced Features ..................................................................................... 1-1 2. Operation ..........................................................................................................
1. SNMP Card................................................................................. 3-13 2. Programmable Relay I/O Card.................................................... 3-14 3. ModBUS Card............................................................................. 3-16 3-4 Other Optional Accessories......................................................................... 3-17 1. Environmental Sensor ................................................................ 3-17 2. SNMP + Switching Hub .
Contents 7. Display and Configuration................................................................................ 7-1 7-1 Control Panel .............................................................................................. 7-1 7-2 LCD Display ................................................................................................ 7-2 7-2-1 LCD Display Hierarchy..................................................................... 7-2 7-3 Default Screen....................................
0. Important Safety Instructions z z z z z z z z z z z z z z z z - This manual contains important instructions for the unit that should be followed during installation and maintenance of the UPS and batteries. All safety and operating instructions should be read thoroughly before attempting to wire or operate the unit. Install the on-line UPS in a well ventilated area, away from flammable liquids and gases. Do not let the unit come in contact with water.
1ΗIntroduction 1. Introduction DELTA NH Plus Series UPS is designed for large-scale power systems applied in data center, communication, networking, medical, safety and emergency systems and all factory facilities. With innovative PFC design and IGBT architecture, the NH Plus Series features high efficiency, low iTHD, low noise and high reliability. The NH Plus Series has a modular structure and hot-swappable function to easily perform maintenance and reduce the MTTR (Mean Time to Repair).
2. Operation There are four basic operation modes for DELTA NH Plus Series. 2-1 Normal Mode (Single Installation) Fig. 2-1 Normal Mode (Single) In normal mode, DC power rectified from AC input power charges batteries and powers the inverter that transforms DC power to stable and clean AC power for various loads. The “Double Conversion” technology allows regulating the utility to provide pure and stable power to your precious equipment (Refer to Fig. 2-1). 2-2 Backup Mode (Single Installation) Fig.
2ΗOperation When a power event (blackout, transient, surge, fluctuation…) occurs, the UPS will automatically transfer from normal mode to backup mode. The battery will provide emergency power to the inverter and then to the loads (Refer to Fig. 2-2). 2-3 Bypass Mode (Single Installation) Fig.
2-4 Manual Bypass Mode (Single Installation) Fig. 2-4 Manual Bypass Mode (Single) In maintenance or repair service condition, you will need to cut off the UPS power but not the power to your equipment. Make sure if the bypass power exists first, then manually switch the UPS to manual bypass mode. At this time, there is no power inside the UPS. The service engineer can do the maintenance or repair task safely but keep your equipment supplied (Refer to Fig. 2-4).
2ΗOperation 2-5 Normal Mode (Parallel) DELTA NH Plus Series provides a parallel combination (up to 4 units) to get redundancy or expand the total capacity. Fig. 2-5 Normal Mode (Parallel) Under this installation, the load is shared by two UPS units. If there is any problem in one of them, the load will be entirely handled by the other. In case the load is greater than one UPS can take, the UPS will shut down and then transfer to the bypass mode (Refer to Fig. 2-5).
2-6 Backup Mode (Parallel) Fig. 2-6 Backup Mode (Parallel) The load is shared by two UPS units when a blackout occurs (Refer to Fig. 2-6).
2ΗOperation 2-7 Bypass Mode (Parallel) Fig. 2-7 Bypass Mode (Parallel) The same as what mentioned in Section 2-3 except two UPS units sharing the load (Refer to Fig. 2-7).
2-8 Manual Bypass Mode (Parallel) Fig. 2-8 Manual Bypass Mode (Parallel) The same as what mentioned in Section 2-4 except two UPS units sharing the load. Remember that both UPS should transfer to manual bypass mode (Refer to Fig. 2-8).
2ΗOperation 2-9 Hot Standby Redundancy The configuration of hot-standby redundancy is to use the identical UPS as the bypass source of single UPS. This installation will make sure if the output power for load is still present even when the main UPS malfunctions (Refer to Fig. 2-9). Fig.
3.
3ΗGeneral View 3-1-1 Dimension 910±1 1165±5 520±1 Fig. 3-1 Power Unit (80KVA) Fig.
Fig. 3-3 External Battery Pack (26AH) Fig.
3ΗGeneral View 3-2 Function Introduction 3-2-1 Front Panel z LCD Display z Control Panel z Status LED Indicators Power Modules I/P and O/P Protectors 1. LCD Display and Control Panel / Status LED indicators - UPS status and message display. - Parameter settings and button control. - UPS startup / shutdown. - EPO: Emergency power off. For more details, refer to Section 6-1. 2. Power Modules - Bezel can be easily removed for maintenance.
3-2-2 Rear Panel Interface Power Modules Wiring Terminal Block Caster & Stop Fig. 3-5 Rear view of NH Plus 1. Interfaces Provide multi-interface for monitoring and control purpose. There are: (1) Two multi-function slots (SNMP card, Relay I/O control card and Mobus card are optional accessories). (2) Parallel port. (3) Input and output dry contacts. (4) RS232: Delta software ”UPSentry Smart 2000” or “Insight Power Manager” is the optional choice for central monitoring and control purpose.
3ΗGeneral View - Remove the cover, then you can perform wiring for input, output and external battery. - Input power source: 3 phases (R, S, T and neutral N). - Bypass input source: 3 Phases (R, S, T and neutral N). - External battery pack: positive (+), negative (-) and neutral N. - UPS output: 3 Phases (R, S, T and neutral N). - Protection Earth: For safety considerations. Different regions may have their own markings of power phases. The following table is a cross reference for possible use.
4. Wiring Terminal Block - You can remove the cover to perform the connection. - Terminal: positive(+), negative(-) and neutral (N). - Two blocks for connecting the UPS and the next battery cabinet. Status contact Protector Wiring Terminal Block Caster & Stop Fig.
3ΗGeneral View 3-2-4 Power Module Each power module is an independent 20kVA/16kW unit, consisting of a power factor corrected rectifier, a battery charger and an inverter, with associated monitoring and control circuitry. Status Off Fail On Locking Latch Fig. 3-7 Front View of Power Module Fig. 3-8 Rear View of Power Module Fig. 3-9 Top View of Power Module CAUTIONS! Power Modules are heavy (~30kg). Two people are required for handling.
3-3 Interface Fig. 3-10 Interface 3-3-1 Dry Contact Input P1: REPO (Remote Emergency Power Off) P2: Dry contact input (Two sets) P3: External Battery Cabinet Temperature 1 P4: External Battery Cabinet Temperature 2 P5: External Battery Cabinet Temperature 3 P6: External Battery Cabinet Temperature 4 P7: External Battery Status 1. P1: REPO 1 The NH Plus Series provides a convenient method for 2 users remotely power off the UPS if an emergency event occurs.
3ΗGeneral View 2. P2: Dry Contact Input (Two sets) The NH Plus Series UPS provides two sets of dry contact input to receive external signals and then the UPS can take corresponding response. These contacts belong to “normal open” type. 1 2 3 4 12V 12V 1 4 2 3 1 4 2 3 Fig. 3-12 Dry Contact Input 3. P3~P6: External Battery Cabinet Temperature You can order the optional accessory “sensor kit” to detect the temperature of external battery cabinet. 4.
3-3-2 Dry Contact Output COMM_A +12VS 1 3 DRYA_NO 2 4 COMM_B +12VS 1 3 DRYB_NO 2 4 COMM_C 1 2 4 DRYC_NO COMM_D DRY3 +12VS 1 3 2 4 DRYC_NO COMM_E DRY4 +12VS 1 3 2 4 DRYE_NO COMM_F DRY5 +12VS 1 3 DRYF_NO 2 4 Fig.
3ΗGeneral View The NH Plus Series UPS provides 6 dry contact outputs. These contacts can be set to Contact Message Description Pin1-2 Load on inverter The UPS is working normally. Pin3-4 Load on auto bypass The UPS is in bypass mode. Pin5-6 Pin7-8 Mains1 input fails when loading on inverter Battery low Pin9-10 Bypass input abnormal The Utility is blackout or abnormal. The UPS is in backup mode. The UPS is in backup mode, and the battery voltage is closed to the terminative limit.
3-3-3 RS232 Port Use a RS232 cable to connect the computer. DELTA develops various powerful software such as “UPSentry Smart 2000” and “InsightPower Manager” to integrate the UPS into your system. For more details, refer to Chapter 7. 5 9 4 8 3 7 2 6 1 TX RX Fig. 3-14 RS232 3-3-4 Parallel Port For redundancy or expansion installation, you simply connect two UPSs via a parallel communication cable. Use the parallel communication cable in the accessory pack.
3ΗGeneral View 1. SNMP Card (Part No.: 3915100120-S) Golden Finger: 12V DC, Communicate with UPS. Dip Switch: Normal, Configuration, Pass Through and Sensor modes. Reset: Reset SNMP. card. Console Port: Connect the HyperTerminal for configuration or Sensor Box for environmental monitoring. RJ45 Network Port: 10/100 M Auto-Negotiation Ethernet interface.
ʳ Technical Specification Network Connection RJ-45 Temperature 0~40°C Humidity 10~80% (Relative) Input Power 9~24V DC Power Consumption 1 Watt (Maximum) Dimension (L x W) 130 x 60 mm Weight 58g ʳ ʳ ʳ ʳ Dip Switch Mode SW1 SW2 Mode ON ON Configuration ON OFF For Environmental Sensor OFF ON Pass Through OFF OFF Normal ʳ 2. Programmable Relay I/O Card (Part No.
3ΗGeneral View Technical Specification Input Power 8 ~ 20VDC Temperature 0 ~ 40°C 10 ~ 80 % 1.2 Watt.
3. ModBUS Card (Part No.: 3915100422-S) Features: Translate the UPS RS232 protocol into another RS232 and RS422/485 Modbus protocol. Device ID is adjustable by 8 dip switches. The value is from 0 to 255. The RS422/485 terminal resistor is selectable by using dip-switches and easy to install. Baud rate and parity options are also adjustable by using dip switches. 2 LEDs for indicating communication status.
3ΗGeneral View 3-4 Other Optional Accessories 1. Environmental Sensor (Part No.: 3915100423-S) Features: Real-time temperature/humidity and other environmental condition monitoring. Monitors the status of 4 user-provide contact devices to protect your critical equipments.
Send the e-mail and SNMP trap to notify users. Provides InsightPower Client software to protect public operating systems. Provides InsightPower Manager to monitor all of the UPS information in the network. Provides InsightPower EzSetting software to easily configure for the first time and upgrade firmware. Technical Specification Network Connection RJ-45 Temperature 0~40°C Humidity 10~80% (Relative) Input Power 12V DC Power Consumption 4.5 Watt.
3ΗGeneral View 3-5 Technical Specification Capacity Input 80KVA/64KW Rating Voltage V Voltage Regulation % -25 ~ +20 Input Current Harmonic Distortion (Full Load) % <5 Frequency Hz 50 / 60 PFC (Full Load) > 0.99 Frequency Tolerance Hz Output Voltage V Output Frequency Hz 50 / 60 Total Harmonic (Linear Load) % Љ3 Static % ̈́1 Dynamic % ̈́7 (10% ~ 90% Linear Load) Interior Oscillator Hz ̈́0.
4. Installation and Wiring 4-1 Before Installation Due to different installation environment, we strongly recommend that you read this manual carefully before installation. Only qualified service personnel can perform installation and maintenance. 4-2 Package Inspections External There are some unpredictable situations that can be possibly encountered during UPS transportation. Therefore, we recommend that you immediately inspect the container for any obvious damage or mishandling. Internal 1.
4ΗInstallation and Wiring 3. The carton and the original packaging must remain sealed to prevent any possible damage from mouse or similar creatures. ʳ Connect and power the loading only when the battery is fully charged. The purpose is to make sure that the UPS can provide the backup power to loads when a blackout occurs. ʳ 4-4 Installation Environment and Position ʳ 4-4-1 Handling Safety 1.
Table 4-1 Floor Loading for UPS Input: 220/380 Vac Capacity / Output: 220/380 Vac 80KVA 120KVA Weight (Kg) 259 379 Floor Loading (kg/m2) 548 748 ʳ Table 4-2 Floor Loading for External Battery Packʳ Batteries - 40 pcs Capacity (Ah) 12V/26AH 12V/40AH Weight (kg) 470 700 Floor Loading (kg/m2) 1064 1575 ʳ 4. Attach the balance supporter to the UPS with bolts. Balance Supporter The UPS may topple over under unexpected conditions withoug balance supporter.
4ΗInstallation and Wiring ʳ 4-4-3 Installation Environment 1. The NH Plus series UPS is for in-house use only. The installation space should be conditioned at temperature of 25°C and relative humidity of <90%. And the maximum operation altitude is 3000 m. 2. The circumstance surrounding the UPS should be kept clean. Prevent any possible damage from mouse or similar objects. 3. The NH Plus Series UPS requires good ventilation and heat dissipation. It features fans for heat dissipation.
4-5 Wiring 4-5-1 Preparations 1. De-energize all input (AC or DC) or output power of the UPS before installing cables or making any electrical connection. 2. Ensure that all cables are correctly marked according to the purpose, as well as the polarity, phase and diameter. 3. If the input/output power of the UPS is WYE-WYE (Y connection), ”Neutral” and ”Ground” should not be connected.
4ΗInstallation and Wiring 4-5-2 Wiring (Single Unit) Wiring procedure: Remover Cover Input External Battery Output Grounding Terminal Fig. 4-1 Wiring Terminal 1. Remove the terminal cover at the rear side. See Fig. 4-1. 2. You can see the terminal block with marks as below.
3. The rated voltage of standard model is 220/380VAC, 230/400VAC or 240/415VAC. 4. The battery rating voltage is ±240VDC. 5. Confirm if the input and bypass input circuit breakers (Q1 and Q2) are cut off (Refer to Fig.4-2). 6. Confirm if the manual bypass circuit breaker (Q3) is cut off. 7. Confirm if the output circuit breaker (Q4) of UPS is cut off. 8. According to UPS model you have selected, use suitable cables and lugs (Refer to Table 4-3). 9.
4ΗInstallation and Wiring 4-5-3 Connecting External Battery Cabinet UPS Battery Cabinet Fig. 4-3 Wiring of External Battery Cabinet Connect corresponding terminals (+, N, –) between UPS and external battery cabinet.
External Battery Pack Connection: 40 series connected batteries in each string battery pack of UPS. The neutral wire is connected at the point between No.20 and No.21 battery. Totally three wires are connected to the UPS terminal: positive, negative and neutral wires. When connecting a non-Delta external battery cabinet with the UPS, you must install a non-fuse 3-pole DC breaker and fuses first. Do not use an AC breaker. Please follow the actual discharge current to decide the breaker’s current capacity.
4ΗInstallation and Wiring 4-5-4 Wiring (Parallel Redundancy, Single Input) 1. Confirm if the input and bypass input breaker (Q1 and Q2) are cut off (Refer to Fig. 4-2). 2. Confirm if the manual bypass circuit breaker (Q3) is cut off. 3. Confirm if the output breaker (Q4) is cut off. 4. According to UPS model you have selected, make use of a suitable cable and lug (Refer to Table 4-3). 5. Connect all cables to the right terminal or location as indicated (Refer to Fig. 4-1). 6.
4-5-5 Wiring (Parallel Redundancy, Dual Input) 1. Confirm if the input and bypass input breaker (Q1 and Q2) are cut off (Refer to Fig. 4-2). 2. Confirm if the manual bypass circuit breaker (Q3) is cut off. 3. Confirm if the output breaker (Q4) is cut off. 4. According to UPS model you have selected, make use of a suitable cable and lug (Refer to Table 4-3). 5. Connect all cables to the right terminal or location as indicated (Refer to Fig. 4-1). 6.
5ΗOperating Procedures 5. Operating Procedures 5-1 Startup Procedures (Single Unit) Before starting up the UPS system, be sure to check the following items first. Ensure all circuit breakers are cut off and switched to OFF, as well as the breaker or fuse of the external battery cabinet. Confirm if the locking latch is located at “±”. Confirm if there is no voltage potential between NEUTRAL and Ground.
If the conditions mentioned above are satisfied, follow the steps below to start up. 1. If there is an external battery cabinet, switch the circuit breaker of battery cabinet to ON and confirm if manual bypass protection circuit breaker Q3 is cut off and switched to OFF. 2. Switch on Q2 and Q4. The LCD monitor will start displaying. After initialization, the LCD screen will show ”ON AUTO BYPASS”.
5ΗOperating Procedures 5-4 Manual Bypass Startup Procedures (Single Unit) If the UPS is in normal mode, press the “O” button for 3 seconds until you hear a “beep” and then release the button. The LCD screen will show “SHUTDOWN UPS?”, then select ” to confirm. The UPS will automatically transfer to bypass mode. “YES” and press “ 1. 2. 3. Confirm if the UPS is in bypass mode. Switch on “Q3”. Switch off “Q4”. 1. Only for maintenance purpose, you can manually turn on the bypass switch “Q3”.
5-5 Startup Procedures (Parallel Redundancy) Before starting up the UPS system, be sure to check the following items first. All circuit breakers are cut off and switched to OFF, as well as the breaker or fuse of the external battery cabinet. Confirm if the locking latch is located at “±”. Confirm if there is no voltage potential between NEUTRAL and Ground. Confirm if the input power source matches the rated voltage, frequency, phase and battery of the UPS that you have installed.
5ΗOperating Procedures 6. Repeat Step 5 to start up another UPS. When the inverter voltage of both UPSs activates normally, both UPSs will transfer to normal mode at the same time. 7. Check the output voltage deviation per each phase of each UPS (must be less than 5V). If it is normal, switch on “Q4” of each UPS. 5-6 Shutdown Procedures (Parallel Redundancy) If you need to shut down one of the paralleled UPSs: 1.
5-7 Manual Bypass Startup Procedures (Parallel Redundancy) Only for maintenance purpose, you can manually turn on the bypass switch. If you switch on Q3 under normal status, the inverter will shut down and the output will be supplied by manual bypass source. 5-7-1 Online Mode Transfers to Manual Bypass Mode 1. Press the “O” button of the UPS that you want to shut down for 3 seconds until you hear a “beep” and then release the button.
6ΗPower Module Replacement 6. Power Module Replacement 6-1 Status LED Indicators for Power Module Each power module features one LED to help inform the user about the power module status. LED status: “OFF”: When the locking latch is located at “²”, the power module is inactive. When the locking latch is located at “±” and the main power is turned on, the power module is failed. “FLASHING”: The power module is failed and off line. “ON”: The power module is active.
6-2 Power Module Replacement WARNING! Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and remove system components. WARNING! Before removing any Power Module, ensure that the remaining Power Modules can support the load. Follow the instructions below to replace or install the Power Module in the system. Procedures for Replacing Power Modules 1. Remove the bezel cover of appropriate power module.
6ΗPower Module Replacement Off Off Fail On Fail On Fig.
7. Display and Configuration 7-1. Control Panel 5 2 1 4 3 7 6 9 8 10 11 Fig. 7-1 Control Panel 1. Normal (Green): Lights on when the UPS input power is normal. 2. Battery (Amber): Lights on when the UPS is in backup mode. 3. Bypass (Amber): Lights on when the UPS is in manual bypass mode. 4. Fault (Red): Lights on when any fault occurs. 5. LCD Display: Multi-language display (Chinese tradition/Big5, English) 6. ESC: Page up. 7/8. Configuration: i and j: Cursor up or down. : Confirm settings. 9.
7ΗDisplay and Configuration 7-2 LCD Display NH Plus Series UPS features a user-friendly LCD screen to show messages. 7-2-1 LCD Display Hierarchy Fig.
7-3 Default Screen After the UPS starts up and completes the self test, the screen will show as below. UN I T : # 1 . 1 L OAD UN P R O T E C T E D 2008-10-02 ON AU T O B Y P A S S 11 : 59 : 59 BYPA. MAINS ! PRE S S T O B R OWS E EVENT ( 0 0 4 ) 1. When any event occurs, you will see the sign “!” flashes. You can press “j” to see the details. For example: Press “j” again will go to the next message. If there is no further message, the screen will return to the default screen. 2.
7ΗDisplay and Configuration 7-3-1 Status Display The LCD screen will show different status of the UPS. 1. This message means the loads behind UPS are not powered on. The UPS cuts off the output. Possible causes: - The UPS automatically shuts down by itself. - Manually switch off the output circuit breaker. 2. This message means the loads are supplied by bypass source due to initial startup of the UPS.
3. UN I T : # 1 . 1 S E L F D I A GNO S I S 2008-10-02 11 : 59 : 59 BYPA. MAINS ! PRES S T O B R OWS E EVENT ( 0 0 4 ) This message means the UPS starts up by battery power. 4. UN I T : # 1 . 1 L OAD UN P R O T E C T E D 2008-10-02 ON AU T O B Y P A S S 11 : 59 : 59 BYPA. MAINS ! PRES S T O B R OWS E EVENT ( 0 0 4 ) This message means the UPS is in bypass mode. In the mean time, the main power source and battery are cut off. So the loads may lose power if the bypass source suddenly fails.
7ΗDisplay and Configuration 5. UN I T : # 1 . 1 L OAD P R O T E C T E D 2008-10-02 ON L I N E 11 : 59 : 59 BYPA. MAINS This message means the UPS is operating under normal condition (normal mode). 6. UN I T : # 1 . 1 L OAD P R O T E C T E D 2008-10-02 ON B A T T E R Y 11 : 59 : 59 BYPA. MAINS ! PRES S T O B R OWS E EVENT ( 0 0 4 ) This message means the UPS is in battery backup mode. The loads are supplied by battery power.
7. UN I T : # 1 . 1 L OAD P R O T E C T E D 2008-10-02 BAT 11 : 59 : 59 TEST BYPA. MAINS This message means the UPS is performing the “battery test”. 8. UN I T : # 1 . 1 L OAD P R O T E C T E D 2008-10-02 ON E C O 11 : 59 : 59 BYPA. MAINS This message means the UPS is in ECO (Economic Operation) mode. The loads are supplied by bypass source.
7ΗDisplay and Configuration 9. UN I T : # 1 . 1 L OAD UN P R O T E C T E D 2008-10-02 ON MANUA L B Y P A S S 11 : 59 : 59 BYPA. MAINS ! PRES S T O B R OWS E EVENT ( 0 0 4 ) This message means the UPS is in manual bypass mode. When the service personnel performs the maintenance work, the UPS must transfer to this mode first. In the mean time, the main power source and battery are cut off. So the loads may lose the power if the bypass source suddenly fails.
7-4 Main Menu Press “ ” in default screen will change to the main menu. UN I T : # 1 . 1 L OAD UN P R O T E C T E D 2008-10-02 ON AU T O B Y P A S S 11 : 59 : 59 ME A S U R E UP S S E T U P & C ON T R O L MA I N T E NAN C E Press “j” or ”i” to select the desired item, then press “ MEASURE Use “j” or ”i” to select “Measure”, then press ” Use “j” or ”i” to see all the UPS status. Modulon NH Plus Series 7-9 ” to confirm. ” to confirm.
7ΗDisplay and Configuration UN I T : # 1 . 1 UN I T : # 1 . 1 L OAD UN P R O T E C T E D 2008-10-02 L OAD UN P R O T E C T E D 2008-10-02 ON AU T O B Y P A S S 11 : 59 : 59 ON AU T O B Y P A S S 12 : 10 : 39 L1 -N/ L2 L2 -N/ L3 L2 -N/ L3 Vp h a s e ( V ) 221 . 9 223 . 7 222 . 6 Vl i ne (V) 384 . 5 385 . 8 384 . 9 4 . 1 4 . 2 4 . 0 60 . 0 60 . 0 60 . 0 Vp h a s e ( V ) 221 . 9 223 . 7 222 . 6 Vl i ne (V) 384 . 5 385 . 8 384 . 9 F REQ ( H z ) 60 . 0 60 . 0 60 .
7-5 UPS SETUP Use “j” or ”i” to select “Measure”, then press ” ” to access the “UPS SETUP” menu. Before changing the setting of each SETUP, you have to login first. 1. The login screen is shown at the right. Move the cursor to select your correct ID, then press ” ” to go to the next page. ADMINISTRATOR: Qualified service personnel User: The authorization is only to check the parameter but not to configure. 2. The password consists of 4 digitals.
7ΗDisplay and Configuration a. BYPASS SETUP Use “j” or ”i” to select “BYPASS”, then press ” ” to confirm. 1. Use “j” or ”i” to select “VOLT RANGE” or “FREQ RANGE", then press ” ” to confirm. 2. Use “j” or ”i” to select the voltage range, then press ” ” to confirm. 3. Use “j” or ”i” to select the frequency range, then press ” confirm. ” to Press “ESC” to return to the “UPS SETUP” menu.
b. OUTPUT SETUP Use “j” or ”i” to select “OUTPUT SETUP”, then press ” ” to confirm. All parameters in this segment can only be changed under “Bypass Mode”. UN I T : # 1 . 1 1. Use “j” or ”i” to select the desired item, then press ” ” to confirm. L OAD UN P R O T E C T E D 2008-10-02 ON AU T O B Y P A S S 11 : 59 : 59 OU T P U T S E TUP VO L T ( V ) FREQ ( H z ) 220 50 ON O F F F R E Q C ONV ON O F F R E DUND AN C Y ( P WR UN I T ) 2.
7ΗDisplay and Configuration 4. ECO mode Use “j” or ”i” to select the desired mode, then press ” ” to confirm. 5. Frequency Converter Mode Use “j” or ”i” to select the desired mode, then press ” ” to confirm. 6. Redundancy Use “j” or ”i” to select the desired number for redundancy, then press ” ” to confirm. Press “ESC” to return to the “UPS SETUP” menu.
c. BATTERY SETUP Use “j” or ”i” to select “BATTERY”, then press ” ” to confirm. All parameters in this segment can only be changed under “Bypass Mode”. 1. Use “j” or ”i” to select the desired item, then press ” ” to confirm. 2. Battery Type Use “j” or ”i” to select the desired battery capacity, then press ” ” to confirm. UN I T : # 1 .
7ΗDisplay and Configuration 4. Battery Install Date Use “j” or ”i” to set the installation date, then press ” ” to confirm. 5. Battery Next Replace Date Use “j” or ”i” to set the next replace date, then press ” ” to confirm. (Reach the replace date, the UPS will alarm the message in LCD display.) 6. Battery Test Duration Use “j” or ”i” to select the battery test duration, then press ” ” to confirm. Press “ESC” to return to the “UPS SETUP” menu.
d. CHARGER SETUP Use “j” or ”i” to select “CHARGER”, then press ” ” to confirm. UN I T : # 1 . 1 1. Press ” ” to set the charging current. L OAD UN P R O T E C T E D 2008-10-02 ON AU T O B Y P A S S 11 : 59 : 59 C HA R G E R S E TUP C HA R G E R C U R R E N T ( A ) 2. Press “j” or ”i” to change the charging current, then press ” ” to confirm. Press “ESC” to return to the “UPS SETUP” menu.
7ΗDisplay and Configuration e. PARALLEL SETUP Use “j” or ”i” to select “PARALLEL”, then press ” ” to confirm. 1. Use “j” or ”i” to select the desired item, then press ” ” to confirm. 2. PARALLEL GROUP Use “j” or ”i” to set the UPS group for parallel redundancy installation, then press ” ” to confirm. The setting is just for LBS (Load Bus Synchronization) application. The default setting is group 1. 3.
f. CONTROL & TEST SETUP ” to confirm. Use “j” or ”i” to select “CONTROL & TEST”, then press ” 1. Use “j” or ”i” to select the desired item, then press ” ” to confirm. UN I T : # 1 . 1 L OAD UN P R O T E C T E D 2008-10-02 ON AU T O B Y P A S S 11 : 59 : 59 C ON T R O L & T E S T BA T AU T O T E S T OF F DA I L Y BUZ Z E R D I S AB L E E NA B L E MANUA L B A T WE E K L Y MON T H L Y B I WE E K L Y TEST F OR C E BOO S T CHARG E C L R BAT T E S T RE SUL T BUZ Z E R & L ED T E S T 2.
7ΗDisplay and Configuration 5. Force Boost Charge Press ” ” to execute “FORCE BOOST CHARGE”. UN I T : # 1 . 1 L OAD UN P R O T E C T E D 2008-10-02 ON AU T O B Y P A S S 11 : 59 : 59 C ON T R O L & T E S T B A T AU T O T E S T (This item is only accessible for administrator! The Password will beneeded.
g. LOCAL SETUP Use “j” or ”i” to select “LOCAL SETUP”, then press ” ” to confirm. UN I T : # 1 . 1 1. Use “j” or ”i” to select the desired item, then press ” ” to confirm. L OAD UN P R O T E C T E D 2008-10-02 ON AU T O B Y P A S S 12 : 19 : 59 LOCAL DA T E ( Y - M - D ) & T I ME DA T E F O R MA T 08-10-02 Y - M- D S E R I A L C OM I D US ER P A S S WO R D L ANGUA G E D - M- Y 0 L CD CON T RA S T ADM I N P A S S WO R D 12 : 19 : 59 M- D - Y 5 0000 0000 ᧯ ㅔ ԧ E NG L I S H 2.
7ΗDisplay and Configuration 5. LCD Contrast Use “j” or ”i” to set the contrast of LCD screen, then press ” ” to confirm. (This item is user accessible!) 6. Administrator Password The password consists of 4 digitals. Use “j” or ”i” to select the first number, then press ” ” for the next digital. After all digitals are selected, press ” ” to confirm. 7. User Password The password consists of 4 digitals. Use “j” or ”i” to select the first number, then press ” ” for the next digital.
7-6 Maintenance Use “j” or ”i” to select ”MAINTENANCE” in the main menu, then press “ The first item is the series number of the UPS unit. ” to confirm. 1. Use “j” or ”i” to select the desired item, then press ” ” to confirm. 2. Firmware Version Use “j” or ”i” to select the F/W version item, then press ” ” to confirm. (That will show the firmware version of the system and each power module.) 3. Statistics Use “j” or ”i” to read the statistics data, then press ” ” to confirm. UN I T : # 1 .
7ΗDisplay and Configuration 4. Event Log Use “j” or ”i” to read the event log, then press ” ” to confirm. 5. Advance Use “j” or ”i” to select the “ADVANCED” item, then press ” to confirm. ” The “ADVANCED” item includes “clear statistics”, “clear event log” “firmware upgrade” and “other status monitor for service”. (This item is only accessible for administrator! The Password will be required to confirm again.) Press “ESC” to return to the “Main Menu”.
8.
8ΗPower Management Software 8-2 UPSentry Smart 2000 DELTA develops a power software family to easily integrate the UPS into your system. “UPSentry Smart 2000” supports installing in popular operating systems such as Windows, Linux, FreeBSD…etc.
8-2-1 Flexible Management Functions of UPSentry Smart 2000 “UPSentry Smart 2000” provides the following powerful management functions for administrator of data center, MIS and IDC. 1. Real-Time Monitoring, Record and Analysis Real-Time meters: Provides 4 (single phase) or 12 (3 phases) meters displaying actual values of power. Each meter is can be defined by the user to show different power information (voltage, current, frequency…etc.) or UPS real-time status.
8ΗPower Management Software Shutdown Ev Transmit an audible message Execute External Command Popup Message 3. Overload Alarm Setting Administrator can set two-stage overload limit value between 0%-100%. The warning message will pop up while reaching the load limit. 4. Scheduled Shutdown/Auto Restart UPSentry Smart 2000 can safely shut down the PC and then turn off the UPS. All the process is automatically proceeded to protect precious data, files and equipment.
8-3 InsightPower Manager For large-scale machine rooms or factories, administrator requires centralized monitoring and control for the UPSs. DELTA develops “InsightPower Manager” to reach this purpose. Features: Centralized monitoring and control of the UPS via 3F TCP/IP network Supports RS232, RS485 and SNMP connections. Supports database 2F connection through ODBC. Adopts the hierarchical design that allows unlimited nodes.
8ΗPower Management Software Event Tracking: Records UPS events and operation records by date/time. Allows showing the graphic chart of historical data records that can be saved as EXCEL files. Allows assigning a period to generate a statistical report.
9. Warranty Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship within the warranty period. If the product has any failure problem within the warranty period, Seller will repair or replace the product at its sole discretion according to the failure situation. This warranty does not apply to normal wear or to damage resulting from improper installation, operation, usage, maintenance or irresistible force (i.e.