Product data
DeltaV Product Data Sheet
October 2014 – Page 25 S-Series Electronic Marshalling
Discrete Output 24 VDC High-Side CHARM
Specifications for DO 24 VDC High-Side CHARM
Device Type 24 VDC Solenoid coils
On State Output rating 100 mA continuous @ 24 VDC
Off-state leakage Current 1 mA maximum
Line Fault Detection
• Guaranteed short circuit: <50 Ω load
• Guaranteed good status: 240 Ω to 10 kΩ load
• Guaranteed open circuit: >20 kΩ load
Configurable output behavior
• Momentary Output
• Continuous Pulse Output
• Line fault testing
Line Fault Test timing
200 µsec
Field Circuit Protection - 200 mA Current Limiting Circuit
- Field wiring disconnect
CHARM power req. 116 mA max @ 24 VDC - Standard Terminal Block
24 mA max @ 24 VDC - Relay Output Terminal Block
CHARM Heat Dissipation 0.44 W - Standard Terminal Block
0.61 W - Relay Output Terminal Block
Simplified Circuit and Connection Diagram for DO 24 VDC High Side CHARM
Simplified Circuit and Connection Diagram for DO 24 VDC High Side CHARM
with CHARM Relay Output Terminal Block