Product data

DeltaV Product Data Sheet
October 2014 Page 25 S-Series Electronic Marshalling
Discrete Output 24 VDC High-Side CHARM
Specifications for DO 24 VDC High-Side CHARM
Device Type 24 VDC Solenoid coils
On State Output rating 100 mA continuous @ 24 VDC
Off-state leakage Current 1 mA maximum
Line Fault Detection
Guaranteed short circuit: <50 Ω load
Guaranteed good status: 240 Ω to 10 kΩ load
Guaranteed open circuit: >20 kΩ load
Configurable output behavior
Momentary Output
Continuous Pulse Output
Line fault testing
Line Fault Test timing
200 µsec
Field Circuit Protection - 200 mA Current Limiting Circuit
- Field wiring disconnect
CHARM power req. 116 mA max @ 24 VDC - Standard Terminal Block
24 mA max @ 24 VDC - Relay Output Terminal Block
CHARM Heat Dissipation 0.44 W - Standard Terminal Block
0.61 W - Relay Output Terminal Block
Simplified Circuit and Connection Diagram for DO 24 VDC High Side CHARM
Simplified Circuit and Connection Diagram for DO 24 VDC High Side CHARM
with CHARM Relay Output Terminal Block