Technical information
J-27
Above prices do not include VAT. E&OE
Monitoringdevices
Function Two level liquid level Four probe liquid level Pump protection relay
Model DLL DLL4 DPP1 (single) DPP3 (three phase)
Description of operation
1. Emptying
TherelayoperateswhentheliquidreachestheMAXelectrode
(contact 7), and releases when the liquid is no longer in
contactwiththeMINelectrode(contact9).Contact10mustbe
connecttothecontainer(ifconductive)oraseperateadditional
electrodeshouldbeused.
2. Filling
TherelayreleaseswhentheliquidreachestheMAXelectrode
(contact 7) and operates when the liquid is no longer in
contactwiththeminelectrode(contact9).Contact10mustbe
connecttothecontainer(ifconductive)oraseperateadditional
electrodeshouldbeused.
Single level
Therelay canalsobe usedfor singlelevelcontrol highor low
byonlyconnectingonelevelelectrode.
1. Emptying with AlarmRelay1operateswhenliquidreaches
the MAX1 electrode (contact 7) if liquid continues to fill to the
MAX 2 electrode level relay 2 (alarm) reset when the liquid
dropstobelowtheMIN1electrode(contact11)relay1resets.
Iflevelcontinuesto drop to below MIN 2 levelrelay2(alarm)
willreset.
2. Filling with AlarmRelay1releaseswhenliquidreachesthe
MAX1electrode(contact7)ifliquidcontinuestofilltotheMAX
2electrodelevel relay2(alarm)resetwhentheliquiddropsto
belowtheMIN1electrode(contact11)relay1operates.Iflevel
continues to drop to below the MIN 2 level electrode relay 2
(alarm)resets.
3. Emptying with pump priority Relay1 operates when
liquid levels reaches the MAX1 electrode (contact 7) relay 1
releases when level drops to below MIN 1 electrode (contact
11).IfthelevelreachesMAX2electrode,relay2operatesand
remains energised until level drops to below MIN 2 electrode,
whereafter relay 2 releases. This way the stand-by pump is
activated,emptyingthetankfaster.
4. Filling with pump priority Relay1releaseswhenliquidlevel
reachestheMAX1electrode(contact7)relay1operateswhen
level drops below MIN 1 electrode (contact 11).If the level
drops below MIN 2 electrode (contact 13), relay 2 operates
and remains energised until MAX 2 electrode is reached,
whereafter relay 2 releases. This way the stand-by pump is
activated,fillingthetankfaster.
5. Container filling and well draining with alarm Relay1
operateswhenliquidlevelreachesMAX2inthewell.Relay 1
releaseswhen levelreachesMAX 1inthe containerorMIN 2
inthewellrelay2(alarm)willreleaseiflevelisbelowMIN1(in
container)andMIN2(inwell)
6. Electrode test All indicators are on if the (contact 14 and
contact 13) is in good contact with liquid and the liquid is
sufficientlyconductive. NoLEDindicates thatthepoor contact
(resistancehigherthan80kohm)
Time delay: 1 - 10sec (adjustable) response delay is
incorporated.
The unit monitors the following parameters and responds
accordingly:
Voltage sensing
The relay releases if the supply voltage exceeds or falls
below 15% of the set limit stored during calibration. If the
voltage returns to within 15% of the set value the relay will
automaticallyoperate,startingthepump.
Phase Failure / Sequence
If there is a loss of any phases supplied to the unit the relay
release.If anytwo phasesare reversedtherelaywillrelease.
Therelaywillautomaticallyoperateifthesequenceisrestored
orthephaselossiscorrected.
Overload sensing
If the current exceeds the set limit stored during calibration
the relay will release after a one second delay.The relay will
restartaftera10secondpause.Ifanovercurrentconditionis
detectedthree consecutivetimes theunitwilltrippermanently
untilthepowerisremovedandreapplied.
Underload sensing
The unit will detect a loss of load but detecting the increase
in angular lag between the voltage and the current. The
underloadwill releasethe relayafter a10 secondsdelay.The
relaywillremain offforthe recovery time,afterwhich the unit
willrestartthepump.
Theunitcanbecalibratedfromanun-calibratedstate(allLED
flashing) by pressing the front cover ‘SET’ button. The unit
can be reset (not re-calibrated) from a latched fault state by
pressing the ‘SET’ button. This can only be done three times
in 15 minutes. This limit on restarts applies to non-latching
faults.Tore-calibratetheunit,the‘SET’buttonhastobepress
when the supply is applied to the unit until the POWER LED
stopsflashing.
POWER LED
STATUS LED
RELAY LED
Overvoltage flashing on off
Undervoltage on flashing off
Overcurrent flashing off off
Undercurrent off flashing off
Phasereversal flashing flashing off
Contact8&9open on off off
Startupdelay on off flashing
Pumprunningok on off on
Uncalibrated flashing flashing flashing
Galvanic insulation
110,230,400Vareequippedwithinternaltransformervoltage.(testvolts:2kV)
Range accuracy ±0.5%
Repeat accuracy ±0.2%
Time adjustment viadedicatedcalibratedfrontknob(scaleaccuracy:±5%)
Standard voltages
AC:12,24,48,110,230,400,525V±15%
DC:12,24,48,±15%
Contact rating
10A250Vac
16A250Vac
Consumption
AC:±2.4VA
DC:100mA
Reset time 0.5sec(500mSec)
Insulation
4kVbetweensupply/outputandadjacentcontacts
1kVbetweenopencontacts.
Mechanical life 30millionoperations
Ambient limits (operating)-20+60°C
Dimensions
(H)92mmx(D)64mm(W)35.5mm(2moduleswide) (H)92mmx(D)64mm(W)53.5mm(3moduleswide)
Connection diagram