Technical information
J-26
Above prices do not include VAT. E&OE
Timers & control relays
Timingdevices
Delay on de-energisation Unequal repeating timer Star delta timer Defrost timer Multi start attempt
DOD DUR DSD DDT DMSA
On application of supply the relay
operates. On removal of supply
the pre-set time period begins. On
lapse of the pre-set time period
the relay releases. If supply is
re-applied during the time period
(before relay releases) the time
periodisresetandtherelayremains
on.
Note:
DOD should not be operated
by pulses shorter than 30s. The
supplyshouldbeappliedforalleast
30% of the time period. For these
purposes the relay DMFT, operated
by external contact function, should
be used.
Time Ranges:
Selectableviafrontknobs
Asymmetrical Recycler “ON” time
first. Timerwith two independently
adjustable time ranges one for “on”
period and another for “off” period.
On application of supply the relay
operates and the pre-set “on” time
period begins on lapse of the “on”
period the relay releases for the
seperately pre-set “off” time period.
This cycle continues until supply is
removed.
(By bridging terminals 7 and 9 the
sequence can be reversed with the
”off”timeperiodfirst)
SelectabletimerangeA+B
(viafrontmountedselector)
On application of supply the relay
switches to the “star” position
(contact 2) the pre-set “star” time
period begins. on lapse of the set
time period. The relay returns to a
neutral position for the transition
period (adjustable between 40
- 180ms) whereafter the relay
switches to the delta position
(contact 4) and remains there until
supply is removed.
Time Range
Star:30(or)60s(viafrontselector)
Transition:40-180ms
(adjustable)
Configurable for 4-hour (defrost
cycle every 4 hours) or 8-hour
cycles. On application of supply
the pre-select (1-60min) defrost
cycle begins. Thereafter the device
switches to the cooling cycle
activating the pre-set fan delay
(1-60sec to prevent water splatter
andwarmairblowingintotheroom)
whereafterthefanstarts.
Bridging contacts 7 and 9 changes
to cooling cycle. ideal for testing
purposesor forcuttingdefrost cycle
shortifcontrolledbythermostat.
Time Ranges
Cycle:4hr(or)8hr
(viafrontmountedselector)
Defrost:3-60min
Fan:3-60sec
Multi start attempt unit can be
selected to start 3-8 times before
energizing the alarm relay. The
unit can be supplied with voltages
ranging from 10-30Vdc. Start and
stop time can be adjusted from
1-30sec.
Time Range
Star:0-30sec
Transition:0-30sec(pause)
110,230,400Vareequippedwithinternaltransformervoltage(testvolts:2kV)
±0.5%
±0.2%
viadedicatedcalibratedfrontknob(scaleaccuracy:±5%)
AC:12,24,48,110,230,400,525V±15%
DC:12,24,48,±15%
10-30Vdc
6A250Vac 10A250Vac 6A250Vac 6A250Vac 6A250Vac
AC:±2.4VA
DC:100mA
100mA
0.5sec(500mSec)
4kVbetweensupply/outputandadjacentcontacts
1kVbetweenopencontacts.
N/A
30millionoperations
(operating)-20+60°C
(H)92mmx(D)64mm(W)35.5mm(2moduleswide)
466.00 483.00 438.00 502.00 593.00
TIME RANGE A
NO
ON(adj) OFF(adj)
1
0.3-6s 0.3-6s
2
3-60s 3-60s
3
0.3-6m 0.3-6m
4
3-60m 3-60m
5
0.3-6s 0.3-60s
6
3-60s 3-6s
7
0.3-6s 0.3-60m
8
3-60m 3-6s
TIME RANGE B
NO
ON(adj) OFF(adj)
1
3-60s 3-6m
2
0.3-6m 0.3-60s
3
3-6m 3-60m
4
0.3-60m 0.3-6m
5
3-60m 3-6h
6
0.3-6h 0.3-60m
7
3-60s 3-6h
8
0.3-6h 0.3-60s
TIME RANGE A
NO
1
0.3-6s
2
0.9-30s
3
6-60s
4
0.9-6m
5
0.3-30m
6
6-60m