LRC check:
LRC check is the added sum from “Address” to “Data content”. For example, 01H + 03H + 47H + 00H + 00H + 02H = 4DH, then take
the complementary of 2, B3H.
Command code to write 1 word: 06H
For example, in order to write 1000 (03E8H) in controller 01 (comm. address 01H) at the starting data address 4701H, the command in
ASCII mode is:
ASCII mode:
Response message:
STX ‘:’ STX ‘:’
‘0’ ‘0’ ADR1
ADR0
‘1’
ADR1
ADR0
‘1’
‘0’ ‘0’ CMD1
CMD0
‘6’
CMD1
CMD0
‘6’
‘4’ ‘4’
‘7’ ‘7’
‘0’ ‘0’
Starting data address
‘1’
Starting data address
‘1’
‘0’ ‘0’
‘3’ ‘3’
‘E’ ‘E’
Data content
‘8’
Data content
‘8’
‘C’ ‘C’ LRC CHK 1
LRC CHK 0
‘6’
LRC CHK 1
LRC CHK 0
‘6’
CR CR END 1
END 0
LF
END 1
END 0
LF
Panel Cutout & External Dimensions
1. Panel wall thickness should range from 1mm to 8mm
2. Provide at least 90 mm clearance around the controller for proper ventilation.
(Dimensions are in millimeter and (inch))
DTA 4848
DTA 4896
DTA9648
DTA7272