User manual
6
  Ordering Information 
DT
A
 
Series  DTA : Delta A Series Temperature Controller 
 
Panel Size (W × H) 
4848 : 1/16 DIN W48 × H48mm; 9648: 1/8 DIN W96 x H48; 4896 : 1/8 DIN W48 × H96mm; 
7272 : W72 × H72mm; 9696 : 1/4 DIN W96 × H96mm 
 
Output Selection 
R : Relay output, SPDT (SPST: 1/16 DIN size), 250VAC, 5A 
V : Voltage Pulse output, 14V+10% ~ -20%(Max. 40mA) 
C : Current output, 4~20mA 
 
Communication 
(
O
p
tional
)
0 : No interface 
1 : RS-485 
 
Current Transformer 
(CT) Function 
(Optional) 
None : No CT function (Current transformer is not provided) 
T : Current transformer is provided (only DTA7272 series support this function) 
  Current Transformer (CT) Function 
The Current Transformer (CT) function is used with the alarm output. When using a current transformer (CT) with the controller, change the corresponding alarm 
output mode to mode 13 (alarm output set value is 13), then turn to operation mode and set the current lower-limit and current upper-limit. You can set current 
alarm range between 0.5A ~  30A, display resolution is 0.1A and measure accuracy is +/- 0.5A.  
  Communication Parameters List 
Controller offers a RS-485 port for serial communication. 
•  Supporting transmission speed: 2400, 4800, 9600, 19200, 38400bps 
•  Communication protocol: Modbus (ASCII) 
•  Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2 
•  Available communication address: 1 to 255, 0 is broadcast address 
•  Function code: 03H to read the contents of register (Max. 3 words). 06H to write 1 (one) word into register. 
  Content  Explanation 
4700H (R)  Process value (PV)  Measuring unit is 0.1, updated one time in 0.5 second 
4701H Set point (SV) 
Unit is 0.1,
 o
C or 
o
F 
4702H  Upper-limit alarm 1   
4703H  Lower-limit alarm 1   
4704H  Upper-limit alarm 2   
4705H  Lower-limit alarm 2   
4706H  Upper-limit of temperature range  The data content should not be higher than the temperature range 
4707H  Lower-limit of temperature range  The data content should not be lower than the temperature range 
4708H  PB Proportional band  0.1 to 999.9, unit is 0.1 
4709H  Ti Integral time  0 to 9999 
470AH  Td Derivative time  0 to 9999 
470BH  Heating/Cooling hysteresis  0 to 9999 
470CH~ 470FH  Reserved 
4710H  Input temperature sensor type  Please refer to the contents of the “Temperature Sensor Type and Temperature Range” for detail 
4711H Control method 
0: PID (default), 1: ON/OFF, 
2: manual tuning 
4712H  Heating/Cooling control cycle  1 to 99 second 
4713H  Proportional control offset error value  0% to 100% 
4714H  Temperature regulation value  -999~999, unit: 0.1 
4715H  Alarm 1 type  Please refer to the contents of the “Alarm Outputs” for detail 
4716H  Alarm 2 type  Please refer to the contents of the “Alarm Outputs” for detail 
4717H  Temperature unit display selection 
o
C : 1 (default), 
o
F : 0 
4718H Heating/Cooling control Selection  Heating: 0 (default), Cooling: 1 
4719H  Control Run/Stop setting  Run: 1 (default), Stop:0 
471AH  Communication write-in selection  Communication write in disabled: 0 (default), Communication write in enabled: 1 
471BH  Software version  V1.00 indicates 0 x 100 
4729H  AT Setting  OFF: 0 (default), ON:1 
Code 0  Normal operation (No error) 
Code 1  Initial process 
Code 2  Initial status (Temperature is not stable) 
Code 3  Temperature sensor is not connected 
Code 4  Temperature sensor input error 
Code 5  Measured temperature value exceeds the temperature range 
Code 6  No Int. error 
472BH (R) 
Code 7  EEPROM Error 
4733H  CT monitor value  Unit is 0.1A 
Note: R means “read only” value 