User manual

2
Display, LED and Pushbuttons
PV Display : to display the process value or parameter type.
SV Display : to display set point, parameter operation read value, manipulated variable or set value of the parameter.
AT : flashes when the Auto-tuning operation is ON.
OUT : lights when the output is ON.
: Function key. 1. Press this key to select the desired function mode.
2. Press this key to confirm a setting value.
: Mode key. Press this key to set parameters within each function mode.
o
C,
o
F : Temperature unit LEDs.
o
C LED lights when this parameter is configured for Celsius and
o
F LED lights if configured for Fahrenheit.
ALM1 / ALM2 : Alarm output LED. The ALM1 / ALM2 LED lights when Alarm 1 or Alarm 2 output is ON.
: Up key. Press this key to increase values displayed on the SV display. Hold down this key to speed up the incremental action.
: Down key. Press this key to decrease values displayed on the SV display. Hold down this key to speed up the decrements.
Specifications
Input Voltage 100 to 240VAC 50/60Hz
Operation Voltage Range 85% to 110% of rated voltage
Power Consumption 5VA max.
Display Method
7-segment digit LED Display
Process value (PV): Red color, Set point (SV): Green color
Thermocouple: K, J, T, E, N, R, S, B, U, L, Txk
Sensor Type
3-wire Platinum RTD: Pt100, JPt100
Control Mode PID, ON/OFF control or Manual tuning
Relay output:(resistive load): SPDT (SPST: 1/16 DIN size), 250VAC, 5A
Voltage Pulse output: DC 14V, Max. load current 40mA
Control Output
Current output: 4 to 20mADC (Load resistance: Max. 600Ω)
Display Accuracy 0.1% of measuring range
Sampling Rate 500 msec/per scan
Vibration Resistance 10 to 55Hz, 10m/s
2
for 10min, each in X, Y and Z directions
Shock Resistance Max. 300m/ s
2
, 3 times in each 3 axes, 6 directions
Ambient Temperature
0
o
C
to
+
50
o
C
Storage Temperature
-
20
o
C
to
+
65
o
C
Relative Humidity 35% to 80% (non-condensing)
Altitude 2000m or less
Installation Environment
Installation Category 33, Pollution Degree 2. Conforming to EN61010-1
Parameters List
1. Operation Mode: Perform per the settings of related control parameters
LED Display Explanation Default
RUN/STOP: Control setting begins. Run ( ) or Stop ( ) mode on the SV display.
RUN
ALARM1 HIGH: Upper-limit alarm 1
4.0
o
C
ALARM1 LOW: Lower-limit alarm 1
4.0
o
C
ALARM2 HIGH: Upper-limit alarm 2
4.0
o
C
ALARM2 LOW: Lower-limit alarm 2
4.0
o
C
Setting lock: Lock 1 ( ), Lock 2 ( ) or OFF ( ) on the SV display. Lock 1 mode can lock all settings and Lock 2 mode
only can lock others than SV value. When OFF mode is selected, the Lock function will be OFF. If you press
and key
simultaneously, the “Lock” status can be released and the controller will be back to the previous display.
OFF
OUT: Output value display and output value adjustment in manual tuning control (This function is not available in ON/OFF control or Auto-
tuning setting)
0
CT: In case of using an external current transformer (CT), the controller displays the current value being measured by CT, if the control
output is ON
Read only