Specifications
9
Setting value
Temperature sensor is
not connected
Measured temperature exceeds
temperature range
Unknown input
SV
Alarm Outputs
There are two groups of alarm outputs and each group can select ten alarm types in the initial setting
function mode. The alarm output is activated when the temperature of target (PV) is getting higher or
lower than set value (SV).
Set
Value
Alarm Type Alarm Output Function
0 Alarm function disabled
Output OFF
1
Deviation upper- and lower-limit:
This alarm output operates when PV value is higher
than set value of SV+(AL-H) or lower than set value of
SV-(AL-L).
ON
OFF
SV-(AL-L)
SV
SV+(AL-H)
2
Deviation upper-limit:
This alarm output operates when PV value is higher
than set value of SV+(AL-H).
ON
OFF
SV
SV+(AL-H)
3
Deviation lower-limit:
This alarm output operates when PV value is lower
than set value of SV-(AL-L).
ON
OFF
SV
SV-(AL-L)
4
Reverse deviation upper- and lower-limit:
This alarm output operates when PV value is in the
range of set value of SV+(AL-H) and SV-(AL-L).
ON
OFF
SV
SV-(AL-L)
SV+(AL-H)
5
Absolute value upper- and lower-limit:
This alarm output operates when PV value is higher
than set value of AL-H or lower than set value of AL-L.
ON
OFF
A
L-L 0
A
L-H
6
Absolute value upper-limit:
This alarm output operates when PV value is higher
than set value of AL-H.
ON
OFF
0
A
L-H
7
Absolute value lower-limit:
This alarm output operates when PV value is lower
than set value of AL-L.
ON
OFF
A
L-L 0
8
Deviation upper- and lower-limit with standby
sequence:
This alarm output operates when PV value reaches set
value (SV value) and the value is higher than set value
of SV+(AL-H) or lower than set value of SV-(AL-L).
ON
OFF
SV
SV-(AL-L) SV+(AL-H)
9
Deviation upper-limit with standby sequence:
This alarm output operates when PV value reaches set
value (SV value) and the reached value is higher than
set value of SV+(AL-H).
SV+(AL-H)
ON
OFF
SV