Specifications
8
Temperature Sensor Type and Temperature Range
Input Temperature Sensor Type
Register
Value
LED Display Temperature Range
Platinum resistance (Pt100) type3 15
0.0 to 100.0
Platinum resistance (Pt100) type2 14
-20.0 to 500.0
Platinum resistance (Pt100) type1 13
-200 to 600
Platinum resistance (JPt100) type2 12
0.0 to 100.0
Platinum resistance (JPt100) type1 11
-20.0 to 400.0
Thermocouple (TC) B type 10
100 to 1800
Thermocouple (TC) S type 9
0 to 1700
Thermocouple (TC) R type 8
0 to 1700
Thermocouple (TC) N type 7
-200 to 1300
Thermocouple (TC) E type 6
0 to 600
Thermocouple (TC) T type2 5
-20.0 to 400.0
Thermocouple (TC) T type1 4
-200 to 400
Thermocouple (TC) J type2 3
-20.0 to 400.0
Thermocouple (TC) J type1 2
-100 to 850
Thermocouple (TC) K type2 1
-20.0 to 500.0
Thermocouple (TC) K type1 0
-200 to 1300
Input Error Indication
Setting value
Temperature sensor is
not connected
Measured temperature exceeds
temperature range
Unknown input
PV