 Output Wiring 
Connect 
0V,  CP1 (phase A) and  CP2 (phase B) to CN1 terminal on ASDA-A servo drive 
Assume 
The set value in the CTA counter is 160mm. When the counting reaches 160mm, an output signal will be given 
to the knife for the cutting. See figure 2. 
In the figure, we can see the diameter of the roller is 44.8mm 
Delta encoder 1 phase = 2,500ppr 
Calculate the pre-scale value 
ppr
D
π
 = Prescale 
π: 3.1416 
D: diameter of the roller 
ppr: number of pulses per revolution of the encoder 
Prescale = 
ppr
D
π
 = 
2500
84414163 .x.
 = 0.056mm/pulse 
When the value in CTA = 2,858 
2858 x 0.056 = 160mm (actual moving distance)
Figure 1 
SV has to be 160mm 
Figure 2 
The servo drive stops at 100mm on the ruler before its 
operation 
100mm