ASDA-A User Manual Chapter 5 Trial Run and Tuning Procedure
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4th Edition 2005/11/30, HE03
5-5
4) When display shows:
Reverse limit switch error:
Please check if any of digital inputs DI1~DI8 signal is set to “Reverse inhibit limit (CWL)” and check if
the signal is ON or not.
Corrective Actions:
 If it is no need to use “Reverse inhibit limit (CWL)” as input signal, it only needs to confirm that if all
of the digital inputs DI1~DI8 are not set to “Reverse inhibit limit (CWL)”. (The setting value of
parameter P2-10 to P2-17 is not set to 22.)
 If it is necessary to use “Reverse inhibit limit (CWL)” as input signal, it only needs to confirm that
which of digital inputs DI1~DI8 is set to “Reverse inhibit limit (CWL)” and check if the digital input
signal is ON (It should be ON).
5) When display shows:
Forward limit switch error:
Please check if any of digital inputs DI1~DI8 signal is set to “Forward inhibit limit (CCWL)” and check if
the signal is ON or not.
Corrective Actions:
 If it is no need to use “Forward inhibit limit (CCWL)” as input signal, it only needs to confirm that if
all of the digital inputs DI1~DI8 are not set to “Forward inhibit limit (CCWL)”. (The setting value of
parameter P2-10 to P2-17 is not set to 23.)
 If it is necessary to use “Forward inhibit limit (CCWL)” as input signal, it only needs to confirm that
which of digital inputs DI1~DI8 is set to “Forward inhibit limit (CCWL)” and check if the digital input
signal is ON (It should be ON).
If the “
” show on the display and “digital input 1” is set to Servo On (SON), it indicates that
Servo on (SON) function is enabled.
6) When display shows: