Chapter 3 Configuration and Wiring ASDA-A User Manual
4th Edition 2005/11/30, HE03 © DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
3-24
Setting of parameter P2-10 to P2-17:
DI
Code
Signal Description
33 MD0 Feed step mode input 0
34 MD1 Feed step mode input 1
35 MDP0 Manually continuous operation
36 MDP1 Manually single step operation
37 JOGU Forward JOG input
38 JOGD Reverse JOG input
39 STEPU
Step up input (available in Pr mode
only)
40 STEPD
Step down input (available in Pr
mode only)
41 STEPB
Step back input. (available in
internal auto running mode only)
42 AUTOR Auto run input
43 GNUM0
Electronic gear ratio (Numerator)
selection 0 [see P2-60~P2-62]
44 GNUM1
Electronic gear ratio (Numerator)
selection 1 [see P2-60~P2-62]
45 INHP Pulse inhibit input
DI signal:
For example: If user wants to set DI1 to be servo on, it only needs to set the value of parameter P2-10 to 101
(refer to chapter 7).
Note: 11~17: Single control mode;18~20: Dual control mode; 0: Input function disabled
DO signal:
For example: If users want to set DO1 to be servo ready, it only needs to set the value of parameter P2-18 to
101 (refer to chapter 7).
Note: 0: Output function disabled