ASDA-A User Manual Chapter 12 Application Examples
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4th Edition 2005/11/30, HE03
12-15
Relevant Parameters Description, cont.
Parameter
Communication
Address
Parameter Description
P2-45 022DH Combination Output Signal Delay Time [UNIT: 4msec]
Output signal will hold delay time when position command is completed.
P2-46 022EH Feed Step Number
Range: 2~32
P2-47 022FH Position Deviation Clear Delay Time [UNIT: 20msec]
This function is disabled when its setting value is set to 0.
P2-51 0233H Internal Servo ON setting
Digital I/O Signal Setting
DI Signal Parameter Setting Explanation
DI1 (INDEX0) P2-10 = 128 Feed step selection input 0
DI2 (INDEX1) P2-11 = 129 Feed step selection input 1
DI3 (INDEX2) P2-12 = 130 Feed step selection input 2
DI4 (INDEX3) P2-13 = 131 Feed step selection input 3
DI5 (ORGP) P2-14 = 124 Reference “Home” sensor
DI6 (SON) P2-15 = 101 Servo ON (when the setting value is 137, it is manual
operation function.)
(MDP0) P2-15 = 35 (contact “b”) Manually continuous operation
(MDP1) P2-15 = 36 (contact “b”) Manually single step operation
DI7 (MD0) P2-16 = 33 (contact “b”) Feed step mode input 0
DI8 (MD1) P2-17 = 34 (contact “b”) Feed step mode input 1
DO Signal Parameter Setting Explanation
DO1 P2-18 = 101
DO2 P2-19 = 103
DO3 P2-20 = 109
DO4 P2-21 = 105
DO5 P2-22 = 107
Please refer to “Definition of DO Signals” in the
following section.
Note: Please set parameter P2-08 to 12 before changing the setting value of DI and DO signals.