P1 - 48
HSPD1 1st Speed Setting of High Speed Homing Communication Addr.: 0130H
Default: 1000 Applicable Control Mode: P
Range: 1~2000
Unit: rpm
Z pulse
HSP2
HSP1
P1 - 49
HSPD2 2nd Speed Setting of Low Speed Homing Communication Addr.: 0131H
Default: 50 Applicable Control Mode: P
Range: 1~500
Unit: rpm
P1 - 50 HOF1
Homing Offset Rotation Number Communication Addr.: 0132H
Default: 0 Applicable Control Mode: P
Range: +/-30000
Unit: rev
P1 - 51 HOF2
Homing Offset Pulse Number Communication Addr.: 0133H
Default: 0 Applicable Control Mode: P
Range: +/-max. cnt/rev
Unit: pulse
When the value of HOF1, HOF2 (P1-50, P1-51) is set to 0, “Home” will be determined as
Z-phase pulse or ORGP according to the setting of P1-47. If the value of HOF1, HOF2 (P1-50,
P1-51) is not 0, “Home” will be determined as Z-phase pulse or ORGP plus one offset pulse as
new “Home” (HOF1 x 10000 + HOF2).
P1 - 52 RES1
Regenerative Resistor Value Communication Addr.: 0134H
Range: 10~750 Applicable Control Mode: P/S/T
Unit: ohm
1kW and below 40
201kW and above
P1 - 53 RES2
Regenerative Resistor Capacity Communication Addr.: 0135H
Range: 30~1000 Applicable Control Mode: P/S/T
Unit: Watt
1kW and below 60
1201kW and above