ASDA-A User Manual Chapter 7 Parameters
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4th Edition 2005/11/30, HE03
7-27
P1 - 04 MON1
Analog Monitor Output Proportion 1 (CH1) Communication Addr.: 0104H
Default: 100 Applicable Control Mode: P/S/T
Range: 0~100
Unit: %(full scale)
P1 - 05 MON2
Analog Monitor Output Proportion 2 (CH2) Communication Addr.: 0105H
Default: 100 Applicable Control Mode: P/S/T
Range: 0~100
Unit: %(full scale)
P1 - 06
SFLT
Accel / Decel Smooth Constant of Analog Speed
Command (Low-pass filter)
Communication Addr.: 0106H
Default: 0 Applicable Control Mode: S
Range: 0~1000 (0: Disabled)
Unit: msec
P1 - 07
TFLT
Smooth Constant of Analog Torque Command
(Low-pass smooth filter)
Communication Addr.: 0107H
Default: 0 Applicable Control Mode: T
Range: 0~100 (0: Disabled)
Unit: msec
P1 - 08 PFLT
Smooth Constant of Position Command (Low-pass
filter)
Communication Addr.: 0108H
Default: 0 Applicable Control Mode: P
Range: 0~1000 (0: Disabled)
Unit:
10 msec
1st Speed Command
P1 - 09 SP1
1st Speed Limit
Communication Addr.: 0109H
Default: 100 Applicable Control Mode: S
Range: +/-5000
Unit: r/min
1st Speed Command
In Speed mode, this parameter is used to set speed 1 of internal speed command. For the
decimal place setting of internal speed command, please refer to P2-63.
Default: 100 Applicable Control Mode: T
Range: +/-5000
Unit: r/min
1st Speed Limit
In Torque mode, this parameter is used to set speed limit 1 of internal speed command.