User manual

Chapter 7 Parameters ASDA-A User Manual
4th Edition 2005/11/30, HE03 © DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
7-10
Smooth Filter and Resonance Suppression
Control Mode
Parameter Name Function Default Unit
P S T
Related
Section
P1-06 SFLT
Accel / Decel Smooth Constant of
Analog Speed Command (Low-pass
smooth filter)
0 msec O
6-3-3
P1-07 TFLT
Smooth Constant of Analog Torque
Command (Low-pass smooth filter)
0 msec O
6-4-3
P1-08 PFLT
Smooth Constant of Position Command
(Low-pass smooth filter)
0 msec O
6-2-6
P1-34 TACC Acceleration Time 200 msec O O
6-3-3
P1-35 TDEC Deceleration Time 200 msec O O
6-3-3
P1-36 TSL Accel / Decel S-curve 0 msec O O
6-3-3
P2-23 NCF
Notch Filter Frequency of Resonance
Suppression
1000 Hz O O O
6-3-7
P2-24 DPH
Notch Filter Attenuation Ratio of
Resonance Suppression
0 DB O O O
6-3-7
P2-25 NLP
Low-pass Filter Time Constant of
Resonance Suppression
2 or 5 msec O O O
6-3-7
P2-33ϧ INF Easy Setting of Input Filter 0 --- O O O
6-3-6
P2-49 SJIT
Speed Detection Filter and Jitter
Suppression
0 sec O O
---