ASDA-A User Manual Chapter 6 Control Modes of Operation
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4th Edition 2005/11/30, HE03
6-19
6-3-4 Analog Input Proportional Gain (Scalar)
The analog voltage between V_REF and GND controls the motor speed command. Using with parameter
P1-40 can adjust the speed control ramp and its range.
510
-5-10
3000rpm
5000rpm
-3000rpm
-5000rpm
Analog Input Voltage (V)
The speed control ramp is
determined by parameter P1-40
P1 - 40ϧ
VCM
Max. Analog Speed Command
Communication Addr.: 0128H
Default: rated Applicable Control Mode: P/S/T
Range: 0~10000
Unit: rpm
Note: For example, when P1-40 is set to 2000, the max. rotation speed of analog speed command (10V)
is 2000rpm.