Datasheet
DS_AA15S/D/T_06172014       E-mail: DCDC@delta.com.tw   
http://www.deltaww.com/dcdc 
P2 
Input Characteristics 
Parameter  Model  Min.  Typ.  Max.  Unit 
Input Voltage Range 
All Models 
85 
--- 
264 
VAC 
Input Frequency Range 
47 
--- 
440 
Hz 
Input Voltage Range 
120 
--- 
370 
VDC 
Inrush Current (Cold Start at 25℃) 
115VAC 
--- 
--- 
15 
A 
230VAC 
--- 
--- 
30 
A 
Output Characteristics  
Parameter 
Conditions 
Min. 
Typ. 
Max. 
Unit 
Output Voltage Accuracy 
--- 
±1.0 
±2.0 
% 
Line Regulation 
Vin=Min. to Max. 
--- 
±0.5 
±1.0 
% 
Load Regulation 
Iout=Min. to Max. 
Single Output Models 
--- 
±0.5 
±1.0 
% 
Dual/ Triple Output Models 
--- 
±2.5 
±5.0 
% 
Cross Regulation- 
Dual Positives / Triple 
Output 
Vo1 
Measured output Io = 20% to 100% of rated load 
Other output(s) set at 50% of rated load 
--- 
±1.0 
--- 
% 
Vo2 
--- 
±2.5 
--- 
% 
Vo3 
--- 
±2.5 
--- 
% 
Ripple & Noise (20MHz) 
5VDC Output Models  ---  1.5  1.8 
%V
PP
 of 
Other Output Models  ---  0.8  1.0 
%V
PP
 of 
Minimum Load 
--- 
10 
--- 
%Inom. 
Over Voltage Protection 
Zener diode clamp 
--- 
120 
--- 
% of Vo 
Temperature Coefficient 
--- 
±0.01 
±0.02 
%/℃ 
Overshoot 
--- 
--- 
5 
% Vout 
Current Limitation 
Foldback, auto-recovery 
105  ---  ---  %Inom. 
(long term overload condition may cause damage) 
Short Circuit Protection 
Hiccup mode, indefinite (automatic recovery) 
General Characteristics  
Parameter 
Conditions 
Min. 
Typ. 
Max. 
Unit 
I/O Isolation Voltage 
Input to Output, 60 Seconds 
3000 
--- 
--- 
VACrms 
I/O Isolation Resistance 
500 VDC 
100 
--- 
--- 
MΩ 
Switching Frequency 
--- 
100 
--- 
KHz 
Hold-up Time 
--- 
20 
--- 
ms 
MTBF (calculated) 
MIL-HDBK-217F@25℃, Ground Benign 
  280,000 
--- 
--- 
Hours 
EMC Emission 
Conducted and radiated 
EN 55011 class B, EN 55022 class B, FCC part 15 class B 
EMC Immunity according 
EN61000-6-1 
Standard  Specification Requirement 
Performance 
Criteria 
EN61000-4-2 
Air ±8KV Cont. ±4KV 
B 
EN61000-4-3 
80~1000MHz, 10V/m 80% AM, 1KHz 
modulation 
A 
EN61000-4-4 
AC port ±2KV DC, SL, TL ±
2KV not less than 
1 min. 
B 
EN61000-4-5 
1.2/50uS(8/20μS) AC dif. ±1KV DC ±0.5KV 
B 
EN61000-4-6 
0.15~80MHz, 10Vrms (functional earth ports 
included) 
B 
80% AM, 1KHz modulation 
EN61000-4-8 
50Hz/60Hz, 30A/m 
A 
EN61000-4-11 
30%, 10ms 
B 
60%, 100ms, 95%, 5000ms 
C 
Protection Class II 
According IEC/EN 60536 
Safety Approvals 
cUL/UL 60950-1,IEC/EN 60950-1 
UL508 for selective models 