FLUE RUN & FLUE TERMINAL INFORMATION
The SCB Boiler has a fan pressure capable of overcoming 200pa of Flue re-
sistance and Air inlet resistance both added together. See the Table on page 42
for flue part resistances.
Flue positioning should avoid flue products being drawn in by other Boilers see the infor-
mation below. When using separate air intakes these should be at least 600 mm and ide-
ally 1mt away from a flue exhaust. Supply Air can always be taken from an adequately ven-
tilated Boiler Room. Installers must check that Flues comply with the clean air act as defined
by the local authority .
See BS6644 (2005) BS5440 (2000) IGE/UP/10 (ed 2)
Flues must be to current regulations.
600mm
Air Intake
Flue Exhaust
Co Axial Flue
Flue exhaust locations will be the same as those shown on the next page however the 600 mm distance from
the air intakes must be maintained
600mm
Air Intake
Flue Exhaust
600mm
600mm
Co Axial Flue
600mm
Parapet, Wall etc.
600 mm
Co Axial Flue
FLAT SURFACE FLUE POSITIONS
WALL