Operating instructions
11
Checking the running direction
The direction of drive rotation depends on how the three mains phases are connected to the control unit and has to be checked
rst. Proceed as follows:
• Move the door into the semi-opened position using the emergency manual operation function.
• Insert the mains plug of the control unit into the socket or switch the main switch of the control unit on.
• Check that the control is in dead-man mode.
• Use the OPEN and CLOSE buttons to verify whether the running direction of the door corresponds to the buttons pressed.
If the running direction of the door does not correspond with the button commands, change the direction of rotation as
described in the Assembly and Operating Instructions for the control unit. Then check the running direction again.
ElectricconnectiontothecontrolunitandconnectiondiagramforA80AE-A280AE
To connect the drive to the control unit, only use original 12-core control cables which have been approved by the manufac-
turer. The control cable can be plugged in. In order to guarantee strain relief and the protection type, the screw connection
must not be undone. The plugs feature reverse polarity protection and click audibly into place. The yellow/green protective
conductor wire must be connected to the designated push-on connector . Make sure that it engages rmly.
3~230 V
3~230 V
3~400 V
3~230 V
AE-WU
AE-S80
Absolutevalueencoderelectricalinterface:
Plugs (1-6)
1 - Safety chain input
2 - RS485 B
3 - GND
4 - RS485 A
5 - Safety chain output
6 - 7-18 V DC
Terminals (7-12 wired by manufacturer)
7/8 - S4F thermoswitch
9/10 - S3F Safety limit switch HK/LK
(Jumper for AK)
11/12 - Jumper (possible connection point for
external safety elements)