Technical Specifications

46101 Fremont Blvd.
Fremont, CA 94538
tel 1.888.979.9889
www.deltabreez.com
MODEL 80HLED
(Fan with Humidity Sensor/LED Light - 80 CFM)
Description
Low noise ceiling mount ventilating Fan/Light with humidity
sensor rated for continuous running. Fan has been awarded
ENERGY STAR® qualified. It is HVI, UL, and cUL certified, and can
be used to comply with ASHRAE 62.2
(local and whole building continuous and intermittent
operation) ,and CA Title 24 requirements.
DC Motor/Blower
Power rating of 120 volts/60Hz
Brushless DC motor engineered to run continuously
Motor equipped with thermal cutoff fuse
Removable with permanently lubricated plug-in motor
Allows fan to operate in full speed mode or humidity
control mode by cycling ON/OFF switch
For humidity mode, the fan will automatically start when
the humidity level in the room is above 60%.
Built-in soft start function to increase bearingslife
Automatically powers OFF when impeller is locked
abnormally
Self-compensating motor speed for intended airflow when
static pressure is encountered
Housing
Galvanized steel body.
Detachable 4” diameter duct adapter.
Built-in backdraft damper.
Hanger bars included.
Easy installation.
Grille
Attractive design using ABS material.
Attaches directly to housing with torsion springs.
Light
13-Watt LED light output 850 Lumen included, and 90 CRI
Dimmable LED Light(dimmer switch not included)
LED Indicator
Blue and amber LED indicator lights to show humidity
Sensor and full speed modes.
Warranty
3-year limited warranty.
TYPICAL SPECIFICATION
Ventilation fan shall be Delta Breez model 80HLED; ENERGY
STAR qualified with brushless DC motor engineered to run
continuously for a minimum 70,000 hours; airflow rating of 80
CFM and loudness rating of 0.8 Sones at 0.1 static pressure as
certified by the Home Ventilating Institute (HVI); power
consumption of 11 Watts with efficiency rating of 7.2
CFM/Watt at 0.1” static pressure; fan will feature LED indicator
running light, motor lock protection and self-compensating
motor speed for intended airflow when static pressure is
encountered. UL and cUL listed for tub/shower enclosure
when used with GFCI-protected branch circuit wiring.
8
"
8
1
4
"
4"
1
0
3
4
"
10
3
4
"
5
3
4
"
Fan Curve
GreenBuilder 80HLED
4” Duct
(Standard)
Static Pressure (inches w.g.)
0.1
0.25
Air Flow (CFM)
80
63
0.8
1.5
Power Consumption (Watts)
11
13
Energy Efficiency
(CFM/Watt)
7.2
4.8
Current (Amps)
0.3
3
Max
Power Rating (V/Hz)
120 / 60
LED Main Light (Watts)
13
Model
Quantity
Comments
Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
4”Duct (Standard):
80 CFM/0.8 Sones@ 0.1” SP, 11 Watts
63 CFM/1.5 Sones @ 0.25” SP, 13 Watts

Summary of content (1 pages)