Technical Specifications

Fremont, CA 94538 | tel 1.888.979.9889 | www.deltabreez.com
Model
Quantity
Comments
Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
46101 Fremont Blvd.,
MODEL 80F
(80 CFM)
4” Duct (Standard):
80 CFM/0.8 Sones @ 0.1” SP, 10.5 Watts
64 CFM/1.5 Sones @ 0.25” SP, 12.5 Watts
50ft
40ft
30ft
20ft
10ft
0.90
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.25
0.10
Air Pressure (IN H
2
O)
0
0 30.0 60.0 90.0 120.0 150.0
Air Flow (CFM)
Fan Curve
BreezGreenBuilder 80F
4” Duct (Standard)
Static Pressure (inches w.g.) 0.1 0.25
Air Flow (CFM) 80 64
Sones 0.8 1.5
Power Consumption (Watts) 10.5 12.5
Energy Eciency (CFM/Watt) 7.6 5.1
Current (Amps) 0.21 Max.
Power Rating (V/Hz) 120 / 60
Description
Low noise ceiling/wall mount ventilating fan rated for continuous
running. Fan has been awarded ENERGY STAR® qualied. It is HVI,
UL, and cUL certied, and can be used to comply with ASHRAE
62.2 (local and whole building continuous and intermittent
operation), and CA Title 24 requirements.
DC Motor/Blower
Power rating of 120 volts/60Hz
Motor equipped with thermal cuto fuse
Removable with permanently lubricated plug-in motor
Built-in soft start function to increase bearings’ life
Automatically powers OFF when impeller is locked abnormally
Housing
Galvanized steel body
Detachable 4” diameter duct adapter
Built-in backdraft damper
Hanger bars included
Easy installation
Grille
Attractive design using ABS material
Attaches directly to housing with torsion springs
Warranty
3-year limited warranty
TYPICAL SPECIFICATION
Ventilation fan shall be Delta Breez model 80F; ENERGY
STAR qualied with brushless DC motor engineered to run
continuously for a minimum 70,000 hours; airow rating of
80 CFM and loudness rating of 0.8 Sones at 0.1“ static
pressure as certied by the Home Ventilating Institute (HVI);
power consumption of 10.5 Watts with eciency rating of
7.6 CFM/Watt at 0.1” static pressure; fan will feature motor
lock protection and self-compensating motor speed for
intended airow when static pressure is encountered. UL
and cUL listed for tub/shower enclosure when used with
GFCI-protected branch circuit wiring.
4"
8 ¼"
8"
5¾"
10¾”
10¾”