Technical Specifications
46101 Fremont Blvd., Fremont, CA 94538 | tel 1.888.979.9889 | www.deltabreez.com
Model
Quantity
Comments
Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
MODEL 100F
(100 CFM)
4” Duct (Standard):
100 CFM/1.4 Sones @ 0.1 SP, 12.6 Watts
77 CFM/1.5 Sones @ 0.25 SP, 13.5
Watts
50ft
40ft
30ft
20ft
10ft
0.90
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.25
0.10
Air Pressure (IN H
2
O)
0
0 30.0 60.0 90.0 120.0 150.0
Air Flow (CFM)
Fan Curve
BreezGreenBuilder 100F
4” Duct (Standard)
Static Pressure (inches w.g.) 0.1 0.25
Air Flow (CFM) 100 77
Sones 1.4 1.5
Power Consumption (Watts) 12.6
13.5
Energy Eciency (CFM/Watt) 7.9
5.7
Current (Amps) 0.22 Max
Power Rating (V/Hz) 120 / 60
Description
Low noise ceiling/wall mount ventilating fan rated for continuous
running. Fan has been awarded ENERGY STAR® qualied. It is HVI,
UL, and cUL certified, and can be used to comply with ASHRAE
62.2 Intermittent Local Exhaust,and CA Title 24 requirements.
DC Motor/Blower
• Power rating of 120 volts/60Hz
• Brushless DC motor engineered to run continuously
• Motor equipped with thermal cutoff fuse
• Removable with permanently lubricated plug-in motor
• Built-in soft start function to increase bearings’ life
• Automatically powers OFF when impeller is locked abnormally
Housing
• Galvanized steel body
• Detachable 4” diameter duct adapter
• Built-in backdraft damper
• Hanger bars included
• Easy installation
Grille
• Attractive design using ABS material
• Attaches directly to housing with torsion springs
Warranty
• 3-year limited warranty
TYPICAL SPECIFICATION
Ventilation fan shall be Delta Breez model 100F; ENERGY
STAR qualified with brushless DC motor engineered to run
continuously for a minimum 70,000 hours; airflow rating of
100 CFM and loudness rating of 1.4 Sones at 0.1 static pr
essure as certified by the Home Ventilating Institute
(HVI); power consumption of 12.6 Watts with efficiency
rating of 7.9 CFM/Watt at 0.1” static pressure; fan will
feature motor lock protection and self-compensating
motor speed for
intended airflow when static pressure is
encountered. UL and cUL listed for tub/shower enclosure
when used with GFCI-protected branch circuit wiring.
4"
8 ¼"
8"
5¾"
10¾”
10¾”