Support Matrix

Technical specifications
13 Dell EMC XC730xd-12C Series Hyper-Converged Appliance Support Matrix | A24
Type
Specification
Operating
3,048 m (10,000 ft)
Storage
12,000 m (39,370 ft)
Operating altitude de-rating
Up to 35°C (95°F)
Maximum temperature is reduced by 1°C/300 m
(1°F/547 ft) above 950 m (3,117 ft).
35°C to 40°C (95°F to 104°F)
Maximum temperature is reduced by 1°C/175 m
(1°F/319 ft) above 950 m (3,117 ft).
Particulate contamination
NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from
particulates and gaseous contamination. If it is determined that levels of particulates or gaseous
pollution are beyond the limits specified below and are the reason for the damage and/or failures
to your equipment, it may be necessary for you to remediate the environmental conditions that are
causing the damage and/or failures. Remediation of environmental conditions is the responsibility
of the customer.
Air filtration
Data center air filtration as defined by ISO Class 8 per
ISO 14644-1 with a 95% upper confidence limit.
Note:
Applies to data center environments only. Air filtration
requirements do not apply to IT equipment designed to
be used outside a data center, in environments such
as an office or factory floor.
Air entering the data center must have MERV11 or
MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or
other conductive particles.
NOTE: Applies to data center and non-data center
environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a
deliquescent point less than 60% relative humidity.
NOTE: Applies to data center and non-data center
environments.
Gaseous contamination
Note: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by
ANSI/ISA71.04-1985.
Silver coupon corrosion rate
<200 Å/month as defined by AHSRAE TC9.9.
Expanded operating temperature