Support Matrix
Technical specifications
16 Dell EMC XC730 Series Hyper-Converged Appliance Support Matrix | A24
Type
Specification
NOTE: Applies to data center and non-data
center environments.
Gaseous contamination
Note: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by
ANSI/ISA71.04-1985.
Silver coupon corrosion rate
<200 Å/month as defined by AHSRAE
TC9.9.
Expanded operating temperature
NOTE: When operating in the expanded temperature range, ambient temperature
warnings may be reported on the LCD and in the System Event Log.
Continuous operation
5°C to 40°C at 5% to 85% RH with 29°C
dew point.
NOTE: Outside the standard operating
temperature (10°C to 35°C), the system can
operate continuously down to 5°C or as
high as 40°C.
For temperatures between 35°C and 40°C,
derate maximum allowable temperature by
1°C per 175 m above 950 m (1°F per 319
ft).
< 1% of annual operating hours
–5°C to 45°C at 5% to 90% RH with 29°C
dew point