Owners Manual
Convention Power Indicator
Pattern
Condition
CAUTION: When correcting a PSU mismatch, replace only the PSU with the
ashing indicator. Swapping the other PSU to make a matched pair can result in
an error condition and unexpected system shutdown. To change from a High
Output conguration to a Low Output conguration or vice versa, you must turn
o the system.
CAUTION: AC PSUs support both 220 V and 110 V input voltages with the
exception of Titanium PSUs, which support only 220 V. When two identical
PSUs receive dierent input voltages, they can output dierent wattages, and
trigger a mismatch.
CAUTION: If two PSUs are used, they must be of the same type and have the
same maximum output power.
CAUTION: Combining AC and DC PSUs is not supported and triggers a
mismatch.
E Not lit Power is not connected.
Locating Service Tag of your system
Your system is identied by a unique Express Service Code and Service Tag number. The Express Service Code and Service Tag are found
on the front of the system by pulling out the information tag. Alternatively, the information may be on a sticker on the chassis of the
system. This information is used by Dell EMC to route support calls to the appropriate personnel.