Technical specifications
15 Dell EMC XC430 Series Hyper-Converged Appliance Support Matrix | A28
Type
Specification
specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for
you to re-mediate the environmental conditions that are causing the damage and/or failures. Remediation of
environmental conditions is the responsibility of the customer.
Air filtration
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with
a 95% upper confidence limit.
Note: Applies to data center environments only. Air filtration
requirements do not apply to IT equipment designed to be used outside
a data center, in environments such as an office or factory floor.
Air entering the data center must have MERV11 or MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive
particles.
Note: Applies to data center and non-data center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less
than 60% relative humidity.
Note: Applies to data center and non-data center environments.
Gaseous contamination
Note: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver coupon corrosion rate
<200 Å/month as defined by AHSRAE TC9.9.