Technical Guide
Table Of Contents
- Dell EMC PowerEdge R250 Technical Guide
- Contents
- System overview
- System features and generational comparison
- Chassis views and features
- Processor
- Memory subsystem
- Storage
- Expansion cards and expansion card risers
- Power, thermal, and acoustics
- Rack, rails, and cable management
- Supported operating systems
- Dell EMC OpenManage systems management
- Dell Technologies Services
- Dell EMC ProDeploy Enterprise Suite
- Dell EMC Remote Consulting Services
- Dell EMC Data Migration Service
- Dell EMC ProSupport Enterprise Suite
- Dell EMC ProSupport Plus for Enterprise
- Dell EMC ProSupport for Enterprise
- Dell EMC ProSupport One for Data Center
- ProSupport for HPC
- Support Technologies
- Dell Technologies Education Services
- Dell Technologies Consulting Services
- Dell EMC Managed Services
- Appendix A: Additional specifications
- Appendix B. Standards compliance
- Appendix C Additional resources
Table 32. Maximum shock pulse specifications
Maximum shock pulse Specifications
Operating Six consecutively executed shock pulses in the positive and negative x, y,
and z axis of 6 G for up to 11 ms. Six consecutively executed shock pulses in
the positive and negative x, y, and z axis of 6G for up to 11ms.
Storage Six consecutively executed shock pulses in the positive and negative x, y,
and z axis (one pulse on each side of the system) of 71 G for up to 2 ms
Particulate and gaseous contamination specifications
The following table defines the limitations that prevent the damage to the IT equipment and/or, or both failure from particulate
and gaseous contamination. If the levels of particulate or gaseous pollution exceed the specified limitations and results in
equipment damage or failure, you must rectify the environmental conditions. Remediation of environmental conditions is the
responsibility of the customer.
Table 33. Particulate contamination specifications
Particulate contamination Specifications
Air filtration Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
NOTE: This condition applies to data center environments
only. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in
environments such as an office or factory floor.
NOTE: Air entering the data center must have MERV11 or
MERV13 filtration.
Conductive dust Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE: This condition applies to data center and non-data
center environments.
Corrosive dust
● Air must be free of corrosive dust.
● Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
NOTE: This condition applies to data center and non-data
center environments.
Table 34. Gaseous contamination specifications
Gaseous contamination Specifications
Copper Coupon Corrosion rate <300 Å/month per Class G1 as defined by ANSI/
ISA71.04-2013
Silver Coupon Corrosion rate <200 Å/month as defined by ANSI/ISA71.04-2013
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Thermal restrictions
ASHRAE A3/A4 Thermal restriction
The following list is the restriction for supporting fresh air in all the platform.
● Four fans population is required.