Technical Guide
Table Of Contents
- Dell EMC PowerEdge R650xs Technical Guide
- Contents
- System overview
- System features and generational comparison
- Chassis views and features
- Processor
- Memory subsystem
- Storage
- Networking
- Expansion cards and expansion card risers
- Power, thermal, and acoustics
- Rack, rails, and cable management
- Supported Operating Systems
- Dell EMC OpenManage systems management
- Dell Technologies Services
- Dell EMC ProDeploy Enterprise Suite
- Dell EMC Remote Consulting Services
- Dell EMC Data Migration Service
- Dell EMC ProSupport Enterprise Suite
- Dell EMC ProSupport Plus for Enterprise
- Dell EMC ProSupport for Enterprise
- Dell EMC ProSupport One for Data Center
- ProSupport for HPC
- Support Technologies
- Dell Technologies Education Services
- Dell Technologies Consulting Services
- Dell EMC Managed Services
- Appendix A: Additional specifications
- Appendix B. Standards compliance
- Appendix C Additional resources
Environmental specifications
The table below details the environmental specifications for the platform. For additional information about environmental
measurements for specific system configurations, see https://www.dell.com/learn/us/en/uscorp1/product-info-datasheets-
safety-emc-environmental .
An important feature of having a broad menu of different categories is to allow the same platform model to have different
operational ranges depending on the MRD defined.
A list of range categories for different configurations shall be identified by thermal team as early in the project as possible.
Post release, see the Dell EMC PowerEdge Technical Specifications at https://www.dell.com/support/home/en-in//products/
server_int/server_int_poweredge.
Table 29. Operational Climatic Range Categories
Category A2 Allowable Operation
Temperature Ranges (For Altitude <900 meters or 2953 feet) 10 to 35°C (50 to 95°F) with no direct sunlight on the
platform
Humidity Percent Ranges (Non-Condensing at all times) 8%RH with -12°C minimum dew point to 80%RH with 21°C
(69.8°F) maximum dew point
Operational Altitude De-Rating Maximum temperature is reduced by 1°C/300 meters
(1.8°F/984 feet) above 900 meters (2,953 feet)
Table 30. Operational Climatic Range Categories
Category A3 Allowable Operation
Temperature Ranges (For Altitude <900 meters or 2953 feet) 5 to 40°C (41 to 104°F) with no direct sunlight on the
platform
Humidity Percent Ranges (Non-Condensing at all times) 8%RH with -12°C minimum dew point to 85%RH with 24°C
(75.2°F) maximum dew point
Operational Altitude De-Rating Maximum temperature is reduced by 1°C/175meters
(1.8°F/574 feet) above 900 meters (2,953 feet)
Table 31. Operational Climatic Range Categories
Category A4 Allowable Operation
Temperature Ranges (For Altitude <900 meters or 2953 feet) 5 to 45°C (41 to 113°F) with no direct sunlight on the
platform
Humidity Percent Ranges (Non-Condensing at all times) 8%RH with -12°C minimum dew point to 90%RH with 24°C
(75.2°F) maximum dew point
Operational Altitude De-Rating Maximum temperature is reduced by 1°C/125 meters
(1.8°F/410 feet) above 900 meters (2,953 feet)
The table below shows the requirements shared across all environmental categories:
Table 32. Shared Requirements
Allowable Operation
Maximum Temperature Gradient (applies to both operation
and non-operation)
20°C in an hour* (36°F in an hour) and 5°C in 15 minutes
(9°F in 15 minutes), 5°C in an hour* (9°F in an hour) for tape
hardware
Non-Operational Temperature Limits -40 to 65°C (-40 to 149°F)
Non-Operational Humidity Limits (Non-Condensing at all
times)
5% to 95%RH with 27°C (80.6°F) maximum dew point
Maximum Non-Operational Altitude 12,000 meters (39,370 feet)
Maximum Operational Altitude 3,048 meters (10,000 feet)