Installing a power supply module
CAUTION: Many repairs may only be done by a certified service technician. You should only perform
troubleshooting and simple repairs as authorized in your product documentation, or as directed by the online or
telephone service and support team. Damage due to servicing that is not authorized by Dell is not covered by
your warranty. Read and follow the safety instructions that are shipped with your product.
Ensure that the power switch on the power supply module that you are installing, is in the off position.
1. Slide the new power supply module into the chassis until the power supply module is fully seated.
2. Rotate both the release lever toward the chassis until the power supply module locks into place.
3. Connect the power cable to the power supply module and plug the cable into a power outlet.
CAUTION: When connecting the power cable, secure the cable with the cable securing bracket.
NOTE: When installing or hot-swapping a new power supply module, allow several seconds for the system to recognize
the power supply module and determine its status. The power-supply status indicator turns green to signify that the
power supply module is functioning properly.
Cooling fan modules
Your system supports two hot-swappable cooling fan modules.
Removing a cooling fan module
CAUTION:
Many repairs may only be done by a certified service technician. You should only perform
troubleshooting and simple repairs as authorized in your product documentation, or as directed by the online or
telephone service and support team. Damage due to servicing that is not authorized by Dell is not covered by
your warranty. Read and follow the safety instructions that are shipped with your product.
CAUTION: The cooling fans are hot-swappable. To maintain proper cooling while the system is on, replace only
one fan at a time.
NOTE: The procedure for removing each cooling fan module is identical.
Make sure that the Service action allowed indicator lights blue before you remove the cooling fan module. For more
information, see Cooling Fan Module LED Indicator Codes.
NOTE: The Service action allowed indicator LED is not used in server attached configurations.
1. Identify and locate the failed cooling fan module.
CAUTION:
Remove the cooling fan module from the system only if the Service action allowed indicator lights
blue. Removing the cooling fan module from the system when the Service action allowed indicator is off may
damage the system.
NOTE: The Service action allowed indicator LED is not used in server attached configurations.
2. Press the cooling fan module release latch to release the cooling fan module handle.
3. Rotate the cooling fan module handle away from the system, until the cooling fan module is released from the slot.
4. Holding the cooling fan module release handle, pull the cooling fan module away from the chassis.