Dell EMC PowerSwitch Z9332F-ON Setup Guide October 2019
Notes, cautions, and warnings NOTE: A NOTE indicates important information that helps you make better use of your product. CAUTION: A CAUTION indicates either potential damage to hardware or loss of data and tells you how to avoid the problem. WARNING: A WARNING indicates a potential for property damage, personal injury, or death. © 2019 Dell Inc. or its subsidiaries. All rights reserved. Dell, EMC, and other trademarks are trademarks of Dell Inc. or its subsidiaries.
Contents 1 About this guide........................................................................................................................... 4 Related documents................................................................................................................................................................4 Information symbols..............................................................................................................................................................
1 About this guide This guide provides site preparation recommendations, step-by-step procedures for rack mounting and desk mounting, inserting modules, and connecting to a power source. CAUTION: To avoid electrostatic discharge (ESD) damage, wear grounding wrist straps when handling this equipment. NOTE: Only trained and qualified personnel can install this equipment. Read this guide before you install and power up this equipment. This equipment contains two power cables.
NOTE: The Warning icon signals information about hardware handling that could result in injury. NOTE: The ESD Warning icon requires that you take electrostatic precautions when handling the device.
2 Site preparations The Z9332F-ON switch is suitable for installation as part of a common bond network (CBN). You can install the switch in: • • • Network telecommunication facilities Data centers Other locations where the National Electric Code (NEC) applies For more information about the Z9332F-ON switch specifications, see Specifications. NOTE: Install the switch into a rack or cabinet before installing any additional components such as cables or optics.
Switch ground Dell EMC recommends grounding your switch. Use the Z9332F-ON switch in a CBN. Fans and airflow Fan installation is completed as part of the Factory Install based on the stock keeping unit (SKU) type. The Z9332F-ON switch supports AC airflow from the I/O to the PSU or from the PSU to the I/O. The fans ship preinstalled with airflow from the I/O to the PSU. Optionally, you can order and install fans with airflow from the PSU to the I/O.
3 Z9332F-ON Installation To install the Z9332F-ON switch, complete the installation procedures in the order presented in this section. Always handle the switch and its components with care. Avoid dropping the switch or any field replaceable units (FRUs). NOTE: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap when handling the switch and its components.
NOTE: Coat the one-hole lug with an anti-oxidant compound before crimping. Also, bring any unplated mating surfaces to a shiny finish and coat with an anti-oxidant before mating. Plated mating surfaces must be clean and free from contamination. NOTE: The rack installation ears are not suitable for grounding. To connect the ground cable to the switch: 1. Cut the user-supplied ground cable to the wanted length. The cable length must facilitate proper operation of the fault interrupt circuits.
2. Loosen the thumbscrew at the front of the rail assembly. 3. Pull the inner rail out of the rail assembly. 4. Slide the white-plastic lever towards the thumbscrew to separate the inner and outer rails. The lever is marked with a directional arrow. 5. Line up the inner rail with the mounting heads on the switch and attach the rail to the switch.
Slide the rail back until it locks into place. 6. Repeat with the second rail. 7. Align the two outer-rail rear tabs with two rear rackmount slots. 8. Pull the outer rail forward until the rear tabs snap into the rack. 9. Align the two outer-rail front tabs with two front rackmount slots and snap the outer rail into the rack. 10. Slide the switch inner rails into the rack outer rails. 11. Slide the blue-plastic lever towards the rear of the rack to fully insert the switch in the rack.
. Tighten the front thumbscrew on each rail. To remove the switch, loosen the thumbscrews, lift the rail latch, and slide the switch forward. After the switch is almost removed, slide the white-plastic lever towards the thumbscrews to unlock and remove the switch. Optics installation WARNING: When working with optical fibers, follow all warning labels and always wear eye protection. Never look directly into the end of a terminated or unterminated fiber or connector as it may cause eye damage. 1.
• • The input circuits are correctly sized for the loads and that you use sufficient overcurrent protection devices. All protective covers are in place. CAUTION: Do not power up the switch if you did not install a fan module. NOTE: A US AC power cable is included for powering up an AC power supply. You must order all other power cables separately. NOTE: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap when handling the switch and its components.
4 Specifications This section lists the Z9332F-ON switch specifications. CAUTION: Operate the product at an ambient temperature not higher than 45°C (113°F). NOTE: For RoHS information, see Restricted Material Compliance. Topics: • Chassis physical design Chassis physical design Table 1. Chassis physical design Parameter Specifications Height 1.70 inches (43.1 mm) Width 17.26 inches (438.5 mm) Depth 25.88 inches (657.5 mm) Chassis weight with factory-installed components 31 lbs (14.
Parameter Specifications Maximum power consumption 1244.
5 Support The support site provides documents and tools to help you effectively use your equipment and mitigate network outages. Through the support site you can obtain technical information, access software upgrades and patches, download available management software, and manage your open cases. The support site provides integrated, secure access to these services. To access the support site, go to www.dell.com/support/.